–43–

(5)

Oil return control (Electronic expansion valve (SLEV))

• The amount of opening of the oil-return LEV (SLEV) is determined as follows: in cooling, by the operating capacity

of the No. 1 compressor and the ambient temperature; in heating, by the operating capacity of the No. 1 compressor.

• It is opened (64pulses) when both compressors are stopped and started for 10 minutes. (Upper limit of LEV opening

is So = 388 pulse.)

• SLEV = 0 when the No. 1 compressor is stopped.

(6)

Defrosting control

1) Start of defrosting

• After there has been heating operation for 50 minutes or after 90 minutes has passed and a piping temperature

(TH5) of – 8

°

C or less is detected for a preset time, defrosting begins.

• When 10 minutes has passed since the compressor began operation or for forced defrosting (Setting of Dip SW2-

7 on) when 10 minutes has passed since recovery from defrosting forced defrost mode recomes active.

2) End of defrosting

• Defrosting ends when 12 minutes have passed since the start of defrosting, or when a piping temperature (TH5 and

TH7) of 7

°

C or more is detected for 4 minutes or longer. (Note that if the defrost-prohibited time is set on 90 minutes,

the defrost-prohibit time will be 50 minutes following a 12-minute timed recovery.

• Ending the defrosting is prohibited for 4 minutes after the start of defrosting.

3) Defrost-prohibit

• Defrosting is not performed for 10 minutes after the start of compressor operation and during oil recovery mode.

4) Abnormalities during defrosting

• If an error is detected during defrosting, the defrosting is stopped and the defrost-prohibit time is set to 20 minutes

by the compressor cumulative operating time.