(In the case of M-NET remote controller)

Symptom

Cause

Checking method & countermeasure

1

2

Despite pressing of
remote controller
ON/OFF switch,
operation does not
start and there is no
electronic sound.

(No powering signal

appears.)

At about 10 seconds
after turning remote
controller operation
switch ON, the
display distinguishes
and the operation
stops.

1) M-NET transmission power source is not supplied

from outdoor unit.

1

Main power source of outdoor unit is not
connected.

2

Disconnection of connector on outdoor unit circuit
board.
Main board

: CNS1, CNVCC3

INV board

: CNAC2, CNVCC1, CNL2

3

Faulty power source circuit of outdoor unit.
• Faulty INV board,
• Blown fuse (F1 on INV board)
• Broken diode stack
• Broken resistor (R1) for rush current protection

2) Short circuit of transmission line.
3) Erroneous wiring of M-NET transmission line at outdoor unit.

1

Transmission line disconnection or slipping off from terminal
block.

2

Erroneous connection of indoor/outdoor transmission line to
TB7.

4) Disconnection of transmission wiring at remote controller.
5) Faulty remote controller.

The cause of 2) and 3) is
displayed with self-diagnosis
LED for 7102 error.

1) Power source is not fed to indoor unit from transformer.

1

Main power source of indoor unit is not turned on.

2

Disconnection of connector (CND, CNT, CN3T) on indoor controller board.

3

Blown fuse on indoor controller board.

4

Faulty or disconnected transformer of indoor unit.

5

Faulty indoor controller board.

2) Faulty outdoor control circuit board uncontrolled.

As normal transmission is fails between indoor and outdoor units, outdoor unit model can not be
recognized.

Checking method & countermeasure

a) Check transmission terminal block of

remote controller for voltage.
i) In case of 17 ~ 30V

Faulty network remote controller

ii) In case of less than 17V

See “Transmission Power Circuit

(30V) Check Procedure”.

Check indoor LED3

Lighting?

Check for the change of LED
display by operating dip switch
SW1 for self-diagnosis.

Extinguishing or
unable to confirm

Check indoor unit

power source terminal

block voltage

AC 220~240V?

Check fuse on circuit
board

Blown?

Check connection of con-
nector (CND, CNT, CN3T)

Disconnected

Check transformer
resistance value

Within rated?

Check self-diagnosis
function of outdoor unit

Changed?

Faulty indoor
controller board

Check main power source
of power source wiring.

Apply power
source again.

Check 220V~240V
circuit for short circuit
and ground fault.

Improper connector
connection

Check cause of trans-
former disconnection.
•Ground fault on circuit

board

•Ground fault on

sensor, LEV

Check self-diagnosis function af-
ter powering outdoor unit again.

Changed?

Accidental
trouble

Faulty outdoor unit
control circuit board

Repair
faulty point.

NO

YES

YES

NO

NO

YES

YES

NO

NO

YES

YES

Lighting

*1 Check the transformer in accordance with the “TROUBLE SHOOTING” in the indoor unit’s service handbook.

NO

*1