Checking

code

7102

7105

7107

7111

7130

Meaning, detecting method

Cause

Checking method & Countermeasure

Connected unit count over

Address setting error

Erroneous setting of OC unit
address

Erroneous setting of BC con-
troller address

Trouble source :
Outdoor unit
BC controller

Branch No. setting error
Can not operate because branch
No. of indoor unit wrongly set.

Trouble source :
BC controller

Remote control sensor error
Error not providing the tempera-
ture designed to remote control-
ler sensor.

Trouble source :
Indoor unit

Different Indoor model and BC
controller connected error

2) The Outdoor unit address is being

set to 51~100 under automatic ad-
dress mode (Remote controller dis-
plays “HO”).

3) Disconnection of transmission wir-

ing at Outdoor unit.

4) Short circuit of transmission line in

case of 3) & 4), remote controller
displays “HO”.

5) Disconnection of transmission wir-

ing at BC controller.

6) BC controller not for the BIG R2

(model: FA, FB type) is connected.

1) Setting error of Outdoor unit ad-

dress.
The address of Outdoor unit is not
being set to 51~100.

2) The address of BC controller is not

being set within 51~100.

1) Indoor unit capacity per connector

joint is exceeded as follows:
Single connection

:

81 or more

Two connection joint

:

161 or more

Three connection joint

:

241 or more

Four connection joint

:

321 or more

2) Four or more indoor units are set

for the same connection.

3) The smallest branch No. has not

been set when used at joint.

4) Does the address of BC controller

(slave) become the least address +
50 of Indoor controller connecting
to BC controller (slave)?

5) The address of Indoor Unit, which

is connected to BC controller
(slave), sets up the small address
from the greatest address of Indoor
Unit which is connected to BC con-
trol (master).

1) In case when the old type remote

controller for M-NET is used and the
remote controller sensor is de-
signed on indoor unit. (SW1-1
turned ON)

A indoor unit not for the R407C (model:
P•••) is connected.

d) Check for the model total (capacity code total)

of indoor units connected.

Check that the address of OC unit is being set to
51~100.
Reset the address if it stays out of the range, while
shutting the power source off.
When BC controller is out of the range, reset it while
shutting the power source of both OC unit and BC
controller off.

a) Check indoor unit connection No. in refrigerant

circuit.

1

No four or more indoor units which are set

for the same branch No. A?

2

Check total capacity of indoor units which

are set for the same branch No. Judged as
trouble when it applies to Cause 1).

3

Check whether the smallest branch No. is

set when used at joint.

b) Check whether indoor unit capacity code (SW2)

is wrongly set. (Keep factory shipment condition.)
For erroneous switch setting, modify it, turn off
the power source of outdoor unit, and indoor unit
simultaneously for 5 minutes or more, and then
turn on.

C) Verify the address of BC controller (slave) and

Indoor Unit.

a) Replace the old remote controller by the new

remote controller.

Use the P••• indoor unit.