–33–

[2] Test Run Method

Operation procedure

1

Turn on universal power supply at least 12 hours before starting

Displaying “HO” on display panel for about two

minutes

2

Press TEST RUN button twice

Displaying “TEST RUN’’ on display panel

3

Press

selection button

Make sure that air is blowing out

4

Press

select button to change from cooling to heating operation, and vice versa

Make sure that

warm or cold air is blowing out

5

Press

adjust button

Make sure that air blow is changed

6

Press

or

button to change wind

Make sure that horizontal or downward blow is adjustable.

7

Make sure that indoor unit fans operate normally

8

Make sure that interlocking devices such as ventilator operate normally if any

9

Press ON/OFF button to cancel test run

Stop operation

Note 1: If check code is displayed on remote controller or remote controller does not operate normally.

2: Test run automatically stops operating after two hours by activation of timer set to two hours.

3: During test run, test run remaining time is displayed on time display section.

4: During test run, temperature of liquid pipe in indoor unit is displayed on remote controller room temperature

display section.

5: When pressing

adjust button, depending on the model, “NOT AVAILABLE” may be displayed on remote

controller. However, it is not a malfunction.

6: When pressing

or

button, depending on the model, “NOT AVAILABLE” may be displayed on

remote controller. However, it is not a malfunction.