Checking

code

6607

(continued)

Meaning, detecting method

System
compo-

sition

Generating

unit address

Display of

trouble

Detecting

method

Cause

Checking method & countermeasure

No ACK error

When no ACK signal is detected in 6 continuous times with 30 second
interval by transmission side controller, the transmission side detects error.

Note:

The address/attribute shown on remote controller indicates the
controller not providing the answer (ACK).

1

Outdoor
unit (OC)

2

BC
controller

(BC)

3

BC
controller

(BS)

4

Indoor
unit (IC)

5

Remote
controller
(RC)

Remote
control-
ler (RC)

Remote
control-
ler (RC)

Remote
control-
ler (RC)

Remote
control-
ler (RC)

Remote
control-
ler (RC)

No reply
(ACK) at
OC
transmis-
sion to BC

No replay
(ACK) at
BC
transmis-
sion to IC

No reply
(ACK) at
BC
transmis-
sion to BC

No reply
(ACK) at IC
transmis-
sion to RC

No reply
(ACK) at
RC
transmis-
sion to IC

As same that for single refrigerant system.

As same that for single refrigerant system.

As same that for single refrigerant system.

1) Cause of 1) ~ 5) of “Cause for single refriger-

ant system”.

2) Disconnection or short circuit of transmission

line of OC terminal block for centralized con-
trol (TB7).

3) Shut down of OC unit power source of one

re-frigerant system.

4) Neglecting insertion of OC unit power supply

connector (CN40).

5) Inserting more than 2 sets of power supply

connector (CN40) for centralized control use.

For generation after normal operation conduct-
ed once, the following causes can be consider-
ed.

• Total capacity error

(7100)

• Capacity code setting error

(7101)

• Connecting set number error

(7102)

• Address setting error

(7105)

1) Cause of 1) ~ 3) of “Cause for single refri-

gerant system”.

2) Disconnection or short circuit of transmission

line of OC terminal block for centralized con-
trol (TB7).

3) Shut down of OC unit power source of one

Same as measure for single refrigerant
system.

Same as measure for single refrigerant
system.

Same as measure for single refrigerant
system.

a) Shut down the power source of both

IC and OC for over 5 minutes simul-
taneously, and make them again.
Normal state will be returned incase
of accidental trouble.

b) Check for 1) ~ 5) of causes. If cause

is found, remedy it.

c) Check other remote controller or OC

unit LED for troubleshooting for
trouble.

Trouble

Modify the trouble ac-
cording to the content
of check code.

No trouble

Faulty indoor con-
troller

a) Shut down the power source of OC

for over 5 minute, and make it again.
Normal state will be returned in case
of accidental trouble.

b) Check for 1) ~ 5) of causes. If cause

is found, remedy it.
When normal state can not be ob-
tained, check 1) ~ 5) of causes.

(2) Group operation system using plural refrigerants