MITSUBISHI ELECTRIC P500YMF-C User Manual

Page 29

background image

–27–

(2) Indoor unit

DIP SW1, 3

Model

P71

P80

P100

P125

P140

P200

P250

Capacity (model name) code

14

16

20

25

28

40

50

SW2 setting

Model

P20

P25

P32

P40

P50

P63

Capacity (model name) code

4

5

6

8

10

13

SW2 setting

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to the

table below.)

Note 2: The DipSW setting is only effective during unit stopping (remote controller OFF) for SW1, 2, 3 and 4 commonly

and the power source is not required to reset.)

3: When both SW1-7 and SW1-8 are being set to ON, the fan stops at the heating thermostat of OFF.

Setting of DIP SW2

Model

Switch

SW1

SW3

3

6

7

3

4

6

8

PLFY-P

VBM-A

OFF

OFF

VLMD-A VKM-A

OFF

ON

ON

ON

OFF

OFF

ON

ON

PEFY-P

VML-A VMH-A 20~80VMM-A 100~140VMM-A

OFF

OFF

ON

OFF

ON

ON

ON

OFF

OFF

OFF

OFF

ON

OFF

ON

OFF

ON

ON

OFF

PDFY-P

PFFY-P

PCFY-P

PKFY-P

VM-A

ON

VLRM-A, VLEM-A

OFF

VGM-A

ON

VAM-A VGM-A

OFF

OFF

Indoor unit inlet

None

100h

Ineffective

Fan output display

At stationary heating

Very low speed

SW1-7 setting

Ineffective

Ineffective

Heat pump

None

None

None

1st setting

Down blow B, C

Effective

Built in remote controller

Provided

2500h

Effective

Thermo. ON signal display

Always at heat.

Low speed

Set airflow

Effective

Effective

Cool.only

Provided

Provided

Provided

2nd setting

Horizontal

Ineffective

Room temp. sensor position

Clogged filter detect.

Filter duration

OA intake

Remote display select.

Humidifier control

Heating thermo. OFF airflow

Heating thermo. OFF airflow

Power failure automatic
return

Power source start/stop

Model selection

Louver

Vane

Vane swing function

Vane horizontal angle

Vane angle set for cooling

Heating 4deg up

Always ineffective for PKFY-P.VAM

Not provided for PKFY-P.VAM
Provided for PLFY-P.VGM (ON) setting

Always down blow B,C for PKFY-P.VAM
Horizontal (ON) setting for PLFY-P.VLMD

Ineffective (ON) setting for floor
standing

SW1

SW3

1

2

3

4

5

6

7

8

9

10

1

2

3

4

5

6

7

8

9

10

Switch

SW name

Operation by SW

Switch set timing

OFF

ON

OFF

ON

Remarks

At unit stopping

(at remote

controller OFF)

Cooling capacity saving
for PKFY-P. VAM,
effective/ineffective