MITSUBISHI ELECTRIC P500YMF-C User Manual

Page 56

background image

–54–

YES

YES

NO

YES

YES

NO

NO

NO

(5)

Heating operation

Normal operations

Defrosting operations

Stop

Test run

1. Indoor unit fan very low speed

operations

2. Inverter output 0Hz
3. Indoor unit LEV, oil return LEV

fully closed

4. Solenoid valve OFF
5. Outdoor unit fan stop
6. BC controller solenoid valve

OFF

7. BC controller LEV fully closed

1. Indoor and outdoor unit fan

control

2. Inverter frequency control
3. Indoor unit LEV, oil return LEV

control

4. Solenoid valve control
5. BC controller solenoid valve

control

6. BC controller LEV control

1. Indoor unit fan stop
2. Inverter defrost frequency control
3. Indoor unit LEV fully opened, oil

return LEV fully closed

4. Solenoid valve control
5. Outdoor unit fan stop
6. BC controller solenoid valve control
7. BC controller LEV control

Heating operation

4-way valve ON

Defrosting

operation

Test run start

4-way valve OFF

Thermostat ON

3-minute

restart

prevention

Note : 1

When outdoor unit starts defrosting, it transmits defrost operations command to (BC controller and) indoor unit, and the
indoor unit starts defrosting operations.
Similarly when defrosting operation stops, indoor unit returns to heating operation after receiving defrost end command of
outdoor unit.

Note : 2

Defrosting start condition

: After integrated 50 minutes of compressor operations, and –8˚C: or less outdoor unit coil

temperature. (TH7)

Defrosting end condition

: After 12 minutes of defrosting operation or the outdoor unit coil temperature (TH5 and TH7)

having risen to 7˚C or more.