5] function of dip sw and rotary sw – MITSUBISHI ELECTRIC P500YMF-C User Manual

Page 28

background image

–26–

Function According to Switch Operation

Switch Set Timing

When Off

When On

When Off

When On

SWU 1 ~ 2

SW1

1 ~ 8

Refer to LED monitor display on the outdoor board.

9 ~ 10

SW2

1

2

3

4

5
6
7

8
9

10

SW3

1

2

3

4

5

6
7

8
9

10

SW4

1

2

3
4
5
6
7
8
9

10

-

Centralized control not
connected.
Storing of refrigeration
system connection
information.
Store IC•OC error history.

Ordinary control

-
-

Ordinary control

-

When the CS circuit is
closed, that time is totaled.

-

SW3-2 Function Invalid

Stop all indoor units.

– 8

°

C

7

°

C

Ordinary control

Ordinary control
Ordinary control

-
-

Model 400

SW4-2 Function invalid

-
-
-
-
-
-
-
-

[5] Function of Dip SW and Rotary SW

(1)

Outdoor unit

PURY-P400·500YMF-C.

1

Variable capacity unit

MAIN board

-

Centralized control
connected.
Deletion of refrigeration
system connection
information.
Erase IC•OC error history.

• Refrigerant volume

adjustment operation.

• Ignore liquid level errors

-
-

Start forced defrosting.

-

Timer Reset

-

SW3-2 Function Valid

All indoor units test run
ON.

– 10

°

C

12

°

C

2deg lower than normal

Pump Down Operation
High pressure / 1.5 ~ 2.5 K
higher than normal

-
-

Model 500

SW4-2 Function valid

-
-
-
-
-
-
-
-

Changes as shown below by on

off change

0 %

3 %

6 %

9 %

12 %

– 6 %

– 3 %

0 %

Unit Address Setting
For self diagnosis/
operation monitoring

-

Centralized Control
Switch
Deletion of connection
information.

Deletion of error history.

• Adjustment of Refriger-

ant Volume

• Ignore liquid level errors

-
-

Forced defrosting

-

Reset of the time the CS
circuit is closed.

-

SW3-2 Function Valid/
Invalid
Indoor Unit Test Operation

Defrosting start tempera-
ture .
Defrosting end tempera-
ture.

Target low-pressure
change
Pump Down Function
Target high-pressure
change

-
-

Models

SW4-2 Function valid/
Invalid
Configuration compensa-
tion value

-
-
-
-
-
-
-
-

Switch

Function

During normal
operation when
power is on.

Invalid 2 hours
after compressor
starts.

Before power is turned on.

-

Before power is turned on.

Before power is turned on.

During normal operation when
power is on.

-
-

-

During normal operation when
power is on.

-

During normal operation when
power is on.
When SW3-1 is ON after power is
turned on.
During normal operation when
power is on.
During normal operation when
power is on. (Except during
defrosting)
During normal operation when
power is on.
While the compressor is stopped.
During normal operation when
power is on.

-
-

When switching on the power.

When switching on the power.

When SW4-1 is ON

-
-
-
-
-
-
-
-

During normal
operation when
power is on.

10 minutes or
more after
compressor
starts.

Set on 51 ~ 100 with the rotary switch.*2

Note 1: Factory setting is SWU 1 to 2 = 00, SW3 - 10 = set by model. All other switches are set to OFF.

Note 2: If the address is set from 01 to 50, it automatically becomes 100.