beautypg.com

MITSUBISHI ELECTRIC P500YMF-C User Manual

Page 130

background image

–128–

No

SW

1234567890

Item

Relay output dis-
play 1, Light ON
display

0000000000

0

Inspection display
1, OC error

0000~9999

(Address and error code inverted)

0000~9999

(Address and error code inverted)

0000~9999

1

1000000000 Relay output dis-

play 2

SV4a

SV6a

CH2, 3

52F

Retry op-
eration

Emergency
operation

Com-
pressor
running

Error
delayed

Error

Vaccum op-
eration pro-
tection delay

SV3

SV4

SV5

SV6

SV7, 8

Contact
demand

Night
mode

2

0100000000

(IC also included)

Inspection display
2

3

1100000000 Relay output dis-

play 3

4

0010000000

5

1010000000 Communication

demand capacity

6

0110000000 External signal

Cooling-
only ON

Cooling-
only OFF

Heating-
only ON

Heating-
only OFF

Mixed
ON

Mixed
OFF

Fan

Stop

14 0111000000 BC operation

mode

Permis-
sion stop

Standby

Cooling-
only

Cooling
main

Heating-
only

Heating
main

Demand

15 1111000000 Outdoor unit oper-

ation mode

Initial
start

Cooling-only,
cooling main re-
frigerant recovery

Heating-only,
heating main re-
frigerant recovery

Defrosting Balance

oil

Low oil
recovery

16 0000100000 Outdoor unit con-

trol mode

High
pressure
error 1, 2

Low
pressure
error

NO1 Dis-
charge tem-
perature error

NO2 Dis-
charge tem-
perature error

NO1 Over-
current
protection

NO2 Over-
current
protection

Radiator
thermo
operation

17 1000100000 Outdoor unit error

delay

Over-
current
cut off

INV error Refriger-

ant over-
charge

Composi-
tion sen-
sor error

Oil tem-
perature
error

18 0100100000

TH11
error

TH12
error

TH2
error

TH3
error

TH4
error

TH5
error

TH6
error

TH7
error

19 1100100000

TH9
error

TH10
error

High pres-
sure sen-
sor error

THHS
error

20 0010100000

Machine
No.1

Machine
No.2

Machine
No.3

Machine
No.4

Machine
No.5

Machine
No.6

Machine
No.7

Machine
No.8

Machine
No.9

Machine
No.10

Machine
No.11

Machine
No.12

Machine
No.13

Machine
No.14

Machine
No.15

Machine
No.16

8

0001000000

9

1001000000

Indoor unit inspec-
tion

Machine
No.1

Machine
No.2

Machine
No.3

Machine
No.4

Machine
No.5

Machine
No.6

Machine
No.7

Machine
No.8

Machine
No.9

Machine
No.10

Machine
No.11

Machine
No.12

Machine
No.13

Machine
No.14

Machine
No.15

Machine
No.16

10

12

0101000000

11 1101000000

Indoor unit opera-
tion mode

Machine
No.1

Machine
No.2

Machine
No.3

Machine
No.4

Machine
No.5

Machine
No.6

Machine
No.7

Machine
No.8

Machine
No.9

Machine
No.10

Machine
No.11

Machine
No.12

Machine
No.13

Machine
No.14

Machine
No.15

Machine
No.16

0011000000

13 1011000000

Indoor unit thermo

BC op-
eration
instruct

Restric-
tion ener-
gized

3-minute
restart

7

1110000000 Outdoor unit oper-

ation display

Remarks

Display

LD1

LD2

LD3

LD4

LD5

LD6

LD7

LD8

COMP
operat-
ing

COMP1
start

52C2

21S4a
21S4b

SV1

SV
22/32

Regu-
larly
light ON

Remarks: E: Contents into EPROM M: IC monitor through communication E*: Store in service memory