beautypg.com

MITSUBISHI ELECTRIC P500YMF-C User Manual

Page 100

background image

–98–

1

B

A

Cooling

Heating

Stopped

Defrosting

SVA

ON

OFF

OFF

OFF

SVB

OFF

ON

OFF

OFF

SVC

ON

OFF

OFF

OFF

Mode

Branch port

Normal

Malfunction

CNTR(1)-(3)

Approximately 90

Open or shorted

CN03(1)-(3)

Approximately 1.7

* Disconnect the connector before measurement.

CNTR

CN03

BC Controller control board

Red

Blue

Brown

Brown

4) BC controller transformer

Solenoid valves (SVA, SVB, SVC, SVM1)

Coordination signals output from the board and solenoid valve operations. *SVM is not built in depending on models.

Note 1 : (SVA, SVB, SVC)

SVA, SVB and SVC are turned on and off in accordance with operation mode.

(SVM1)

SVM is turned on and off in accordance with operation mode.

Note 2 : (SVA, SVB, SVC)

(SVM1)

Measure temperature of piping on either side of SVA

1

-

A

Measure temperature at points marked “X”.

Measure temperature of piping on either side of SVB

1

-

B

Operation Mode

Cooling-only

Cooling-principal

Heating-only Heating-principal

Defrosting

Stopped

SVM1

ON

OFF

OFF

OFF

ON

OFF