–42–

Item

At compressor is started

Compressor stopped during cool-
ing or heating mode

After operation has been stopped

During defrosting ((*1) in Fig below)

During oil recovery operation

When low pressure (Ps) has
dropped during lower limit fre-
quency operation(15 minutes af-
ter start)

When the high pressure (Pd) is
risen up during lower limit fre-
quency operation (3 minutes after
starting)

Ps

2.0 kg/cm

2

G

(0.196 MPa)

Pd 24 kg/cm

2

G

(2.35 MPa) and after

30 seconds

* Example of operation of SV1

Compressor

Bypass
solenoid
valve (SV1)

(4-minute)

(2-minute)

(4-minute)

(3-minute)

Start

Thermo.
OFF

Thermo.
ON

Defrost

Stop

2) Bypass solenoid valves (SV1, SV4) [Both SV1 and SV4 are on (open)]

ON

OFF

SV1

ON for 4 minutes

ON

ON for 3 minutes

ON

ON during oil recovery operation af-
ter continuous low-frequency com-
pressor operation.

ON

Ps < 1.0 kg/cm

2

G

(0.098 MPa)

Pd 27 kg/cm

2

G

(2.65 MPa)

OFF

SV4a

Normally ON

3) Capacity control solenoid valve (SV22, SV32). :P500 only

• Operation of solenoid valve

Solenoid valve

SV22

SV32

COMP

SV22

SV32

Coil

Valve

Coil

Valve

OFF

Open

OFF Closed

ON

Closed

ON

Open

Status
Full-load
(Operating at 100 %
capacity)

Un-load
(Capacity control
operation)

Pd 27.5 kg/cm

2

G

(2.70 MPa)

Pd 24 kg/cm

2

G

(2.35 MPa) and
after 30 seconds.

130

°

C

(No. 1 compressor)
115

°

C

(No. 2 compressor)

• Td >

and

• Pd > 20 kg/cm

2

G

(1.96 MPa)

or
Ps < 3.5 kg/cm

2

G

(0.34 MPa)

115

°

C

(No. 1 compressor)
100

°

C

(No. 2 compressor)

Td

When the discharge temperature
(Td) is risen up