–115–

Checking code

Meaning, detecting method

Cause

Checking method & Countermeasure

4260

5101

5102

5103

5104

5105

5106

5107

Cooling fan
abnormality

Thermal sensor abnormality (BC controlled)

If the heat sink temperature (THHS)
100

°

C for 20 minutes or longer just

before the inverter starts.

1

A short in the thermistor or an
open circuit was sensed. The
outdoor unit switches to the
temporary stop mode with re-
starting after 3 minutes, then if
the temperature detected by the
thermistor just before restarting
is in the normal range, restart-
ing takes place.

2

If a short or open circuit in the
thermistor is detected just be-
fore restarting, error code
“5101”, “5102”, “5103”, “5104”,
“5105”, “5106”, “5108”, “5109”
or “5112” is displayed.

3

In the 3 minute restart mode,
the abnormal stop delay LED is
displayed.

4

The above short or open circuit
is not detected for 10 minutes
after the compressor starts, or
for 3 minutes during defrosting
or after recovery following de-
frosting.


If a heat sink (THHS) temperature
of -40

°

C is detected just after the

inverter starts or during inverter
operation.

Discharge
(TH11, TH12)

Low
pressure
saturation
(TH2)

Liquid level
detection
(TH3)

Liquid level
detection
(TH4)

Heat
exchanger
inlet pipe
(TH5)

Ambient
tempera-
ture (TH6)

Heat
exchanger
outlet pipe
(TH7)

Thermal sensor abnormality (Outdoor Unit)

Same as “4230.”

Check the thermistor’s resistance.

Check if the lead wires are pinched.

Check for tearing of the insulation.

Check if a pin is missing on the con-
nector.

Check if a wire is disconnected.

Check the temperature picked up by
the sensor using the LED monitor.
If the deviation from the actual tem-
perature is great, replace the MAIN cir-
cuit board.
(In the case of the THHS, replace the
INV board.)

1) Same as “4230.”

1) Thermistor

2) Lead wires are being pinched.

3) Insulation is torn.

4) A connector pin is missing, or there

is faulty contact.

5) A wire is disconnected.

6) The thermistor input circuit on the

MAIN circuit board is faulty.
(In the case of the THHS, replace
the INV board.)

Short Circuit Detection

Open Circuit Detection

TH11, TH12 240

°

C or higher (0.57 k

)

15

°

C or lower (321 k

)

TH2

70

°

C or higher (1.71 k

)

-40

°

C or lower (130 k

)

TH3

70

°

C or higher (1.71 k

)

-40

°

C or lower (130 k

)

TH4

70

°

C or higher (1.71 k

)

-40

°

C or lower (130 k

)

TH5

110

°

C or higher (0.4 k

)

-40

°

C or lower (130 k

)

TH6

110

°

C or higher (0.4 k

)

-40

°

C or lower (130 k

)

TH7

110

°

C or higher (1.14 k

)

-40

°

C or lower (130 k

)

TH8

70˚C or higher (1.14 k

)

-40

°

C or lower (130 k

)

TH9

70

°

C or higher (1.14 k

)

-40

°

C or lower (130 k

)

THHS

-40

°

C or lower (2.5 M

)

TH10

240

°

C or higher (0.57 k

)

-15

°

C or lower (1656 k

)

Short Detected

Open Detected

TH11

110

°

C or more (0.4 k

)

-40

°

C or less (130 k

)

TH12

110

°

C or more (0.4 k

)

-40

°

C or less (130 k

)

TH15

70

°

C or more (1.14 k

)

-40

°

C or less (130 k

)

TH16

70

°

C or more (0.4 k

)

-40

°

C or less (130 k

)

Check thermistor resistance.

Check lead wire biting.

Check broken cover.

Check coming off of pin at connector.

Check broken wire.

Check sensor sensing temperature. If
it deviates from the actual temerature
seriously, replace control panel.

1) Thermistor trouble.

2) Biting of lead wire.

3) Broken cover.

4) Coming off of pin at connector por-

tion, poor contact.

5) Broken wire.

6) Faulty thermistor input circuit of

control board.

5109

5110

5112

5111

CS circuit
(TH9)

Radiator
panel
(TH HS)

Compres-
sor shell
tempera-
ture
(TH10)

Liquid inlet
(TH11)

Bypass
outlet
(TH12)

Bypass
inlet
(TH15)

Intermedi-
ate section
(TH16)

1. When short (high temp. inlet) or

open (low temperature inlet) of
thermistor is detected during
operation, error stop will be
commenced displaying “5111”
or “5112”, “5113” or “5114”, or
“5115” or “5116.

2. The above detectection is not

made during defrostig and 3-
minute after changing operation
mode.