beautypg.com

9check the composition of the refrigerant – MITSUBISHI ELECTRIC P500YMF-C User Manual

Page 146

background image

–144–

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

Start

Test run all indoor units.

Is the refrigerant

composition of

α

OC

correct? (Note 2)

Finished checking the

composition.

Check TH2, TH9, LPS and the CS
circuit block and correct any malfunc-
tions. (Note 3)

Is the

refrigerant composi-

tion of

α

OC correct?

(Note 2)

Finished checking the

composition.

Check that

R407 is correctly

charged.

(Note 4)

Recharge the refrigerant.
(Note 5)

Finished checking the

composition.

Calibrate the refrigerant composition
of

α

OC. (Note 6)

Are all units operating

stably? (Note 1)

9

CHECK THE COMPOSITION OF THE REFRIGERANT