[4] Location of leaks: Outdoor unit (when heating)

1

Remove any refrigerant from the entire system (outdoor unit, extension piping and indoor units).

Reclaim the refrigerant; do not discharge it into the air.

2

Repair the leaks.

3

After the leaks are repaired, replace the dryer with a new one and extract all of the air from the entire system to

create a vacuum. Then, refill with refrigerant until it reaches the calculated specification (outdoor unit + extension

piping + indoor units). Refer to “Chapter

6

” for more details.