Unlock Codes
The
0' N
screen is seen before entry is allowed to Configuration, Setup and Automatic
Tuning modes.
An unlock code must be correctly selected using the or keys to enter the required
mode. An incorrect entry results in a return to Select Mode. The value of the lock codes only
can be changed from within the modes that they apply to.
Table 7. Lock Code – Entry and Default Values
Description Upper/Main
Display
Lower Display
(or 1
st
Legend)*
1
/
8
DIN Indicator
Units Display
Default values are:
Automatic Tune Mode =
Set-up
mode =
Configuration Mode =
.
0' N
3
*Note:
On Indicators (single line display), this legend is shown for approx 1 second before the
Main display value.
Automatic Tune Mode
Automatic Tune Mode is selected when it is desired to use the Pre-tune and Self-tune
facilities on a controller to assist the user in setting up Proportional band, Integral and
Derivative parameter values. Refer to the following Automatic Tune Mode table.
Pre-tune can be used to set Controller PID parameters approximately. Self-tune may then be
used to optimise the tuning. Pre-tune can be set to run automatically after every power-up
using the Auto Pre-Tune
@/
parameter in Setup Mode.
The AT indicator will flash while pre-tune is operating, and is continuously on
whilst Self-tune is operating. If both Pre-tune and Self-tune are engaged the AT indicator will
flash until Pre-tune is finished, and is then continuously on.
Navigating in Automatic Tune Mode
Press to select the next parameter in the table and or to set the value
required.
Hold down and press to return to Select Mode.
Note:
If there is no key activity for 2 minutes the controller automatically returns to operator
mode
59305, Issue 6 – March 2006
Operating and Information Modes
Page 39