7. Using manual control ensure that the valve is positioned away from its end stops.

8. Follow the instructions in the diagram below. At each stage, allow sufficient settling time

before moving on to the next stage.

Time

Process Vari

able

T

b

Time

Process Vari

able

T

a

START

Apply Power to

the load.

Does the

PV

continuously

Oscillate?

Note the time

interval T

a

Set

):)

= 0.8%

Set

+-/

= T

a

Are the

Oscillations

decaying to

zero?

Multiply

):)

setting by 1.5

END

Note the period

of the decaying

oscillations (T

b

)

Multiply

):)

setting by 1.5

Set

+-/

= T

b

2

No

Yes

Yes

No

The controller is now tuned.

Fine-tuning may be required

to optimise the controllers

Table 31. Manually Tuning Valve Control


Page 120

Manual Tuning

59305, Issue 6 – March 2006