Pyromation Series 610 1_16 DIN User Manual

Page 112

background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual

Table 27. P6010 & P8010 Set Up Mode Parameters

Parameter

Legend

for 1 sec

followed

by

Set

Value

Adjustment Range &

Description

Default
Value

When
Visible

Units

Display

(

1

/

8

Din

Only)

Input Filter Time
constant

"'/

OFF, 0.5 to 100.0 seconds
in 0.5 sec increments

.

Always

/

Process
Variable Offset

""-

±Instrument Span

Always

Raw Process
Variable value

-#

The un-scaled value of the input signal in mV, V or
mA DC as defined by the input range and type.
Resolution to 1 decimal place (e.g. 4.0 to 20.0mA).
This parameter is Read Only

%C@.

= mV, V
or mA

blank

Process High
Alarm 1 value
*

)?

Range Min. to Range Max.
Repeat of Configuration Mode parameter

Range
Max.

'
= ):$

Process Low
Alarm 1 value
*

)'

Range Min. to Range Max
Repeat of Configuration Mode parameter

Range
Min.

'
= ):'

if

alarm

1 only

or

Alarm 1
Hysteresis*

$4

1 LSD to 100% of span (in display units)
on “safe” side of alarm point.
Repeat of Configuration Mode parameter

'
is not
C C

:

Process High
Alarm 2 value
*

)?

Range Min. to Range Max.
Repeat of Configuration Mode parameter

Range
Max.

'
= ):$

Process Low
Alarm 2 value
*

)'

Range Min. to Range Max.
Repeat of Configuration Mode parameter

Range
Min.

'
= ):'

Alarm 2
Hysteresis*

$4

1 LSD to 100% of span (in display units)
on “safe” side of alarm point.
Repeat of Configuration Mode parameter

'
is not
C C

F

Process High
Alarm 3 value
*

)?

Range Min. to Range Max.
Repeat of Configuration Mode parameter

Range
Max.

'
= ):$

Process Low
Alarm 3 value
*

)'

Range Min. to Range Max.
Repeat of Configuration Mode parameter

Range
Min.

'
= ):'

Alarm 3
Hysteresis*

$4

'
is not
C C

*

Process High
Alarm 4 value
*

)?

Range
Max.

'
= ):$

Process Low
Alarm 4 value*

)'

Range Min. to Range Max.
Repeat of Configuration Mode parameter

Range
Min.

'
= ):'

Alarm 4
Hysteresis*

$4

1 LSD to 100% of span (in display units)
on “safe” side of alarm point.
Repeat of Configuration Mode parameter

'
is not
C C

4

1 LSD to 100% of span (in display units)
on “safe” side of alarm point.
Repeat of Configuration Mode parameter

Range Min. to Range Max.
Repeat of Configuration Mode parameter


59305, Issue 6 – March 2006

P6010 & P8010 Model Group

Page 107