beautypg.com

Modbus serial communications, Physical layer, Modbus with no parity – Pyromation Series 610 1_16 DIN User Manual

Page 127: Modbus with even parity, Modbus with odd parity

background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual

13

Character format: Always 8 bits per character.

Modbus Serial Communications

All models support the Modbus RTU communication protocol. Some models also support an

. Where both Modbus and ASCII are supported, the protocol to

be used is selected from Configuration Mode. The RS485 Communications Module must be
fitted into Option Slot A in order to use serial communications.

ASCII communication protocol

Refer to the relevant Model Group Section for the ASCII and Modbus Application Layer
(parameter address/ident information).

For a complete description of the Modbus protocol refer to the description provided at
http://www.modicon.com/ or http://www.modbus.org/

Physical Layer

The Base address, bit rate and character format are configured via the front panel in
Configuration Mode or by using the PC Configurator software.

Physical layer configuration settings possible are:

Data rate:

1200, 2400, 4800 (default), 9600 and 19,200 bps

Parity:

None

(default),

Even,

Odd

The transmitter must not start transmission until 3 character times have elapsed since
reception of the last character in a message, and must release the transmission line within 3
character times of the last character in a message.

Note:

Three character times = 1.5ms at 19200, 3ms at 9600, 6ms at 4800, 12ms at 2400 and
24ms at 1200 bps.


Page 122

Modbus Communications

59305, Issue 6 – March 2006

This manual is related to the following products: