Remote Setpoint Upper Limit
Type: Controller Parameter
Defines the value of the Remote Setpoint when the RSP input signal is at its maximum value
(eg for a 4 to 20mA RSP, the value when 20mA is applied). It may be adjusted within the
range -1999 to 9999; (decimal position same as for process variable input). However, the
RSP value is always constrained within the Setpoint Upper Limit and Setpoint Lower Limits.
Display code =
+-)1
, default value = PV input range maximum.
Also refer to
and
and
Retransmit Output 1 Scale Minimum
Type: General Parameter
Scales a linear output module in slot 1 that has been set up to retransmit PV or SP.
Retransmit Scale Minimum defines the value of the process variable, or setpoint, at which
the output will be at its minimum value. E.g. for a 0 to 5V output, the value corresponds to
0V. It may be adjusted within the range -1999 to 9999; the decimal position is always the
same as that for the process variable input. If this parameter is set to a value greater than
that for Retransmit Output Scale Maximum, the relationship between the process
variable/setpoint value and the retransmission output is reversed.
Display code =
+ '
, default value = Scale Range Lower Limit.
Also refer to
and
Remote Setpoint, Remote Setpoint Input, Remote Setpoint Lower Limit, Remote
Remote Setpoint Offset
Type: Controller Parameter
Used to adjust the Remote Setpoint input value. Positive values are added to the RSP
reading, negative values are subtracted. It is adjustable in the range –1999 to 9999, but is
constrained within the Scale Range Upper Limit and Scale Range Lower Limit.
Display value =
+-)
, default value = 0.
Also refer to Remote Setpoint, Scale Range Upper Limit and Scale Range Lower Limit.
Retransmit Output
Type: General Definition
A linear DC voltage or mA output signal, proportional to the Process Variable or Setpoint, for
use by slave controllers or external devices, such as a Data Recorder or PLC. The output
can be scaled to transmit any portion of the input or setpoint span.
Also refer to Input Span, Master & Slave, Process Variable and Setpoint.
Retransmit Output 1 Scale Maximum
Type: General Parameter
Scales a linear output module in slot 1 that has been set up to retransmit PV or SP.
Retransmit Scale Maximum defines the value of the process variable, or setpoint, at which
the output will be at its maximum value. E.g. for a 0 to 5V output, the value corresponds to
5V. It may be adjusted within the range -1999 to 9999; the decimal position is always the
same as that for the process variable input. If this parameter is set to a value less than that
for Retransmit Output 1 Scale Minimum, the relationship between the process
variable/setpoint value and the retransmission output is reversed.
Display code =
+ $
, default value = Scale Range Upper Limit.
Also refer to Process Variable, Retransmit Output, Retransmit Output 1 Scale Minimum,
Scale Range Upper Limit and Setpoint.
Process Variable, Retransmit Output, Retransmit Output 1 Scale Maximum,