P6010 & p8010 indicators – serial communications, Bit parameters – Pyromation Series 610 1_16 DIN User Manual
Page 119

1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
P6010 & P8010 Indicators – Serial Communications Parameters
The Modbus parameter addresses, and the possible ASCII message types and parameters
indents for the P6010 & P8010 are detailed below.
RO indicates a parameter is read only,
WO indicates a parameter is write only and R/W indicates it can read from or written to.
Communications writes will not implemented if the Communications Write Parameter is
disabled. Refer to the Modbus and ASCII Communications sections of this manual for details
of the protocols used.
Bit Parameters
Bit parameters are not applicable to the ASCII protocol.
Table 29. P6010 & P8010 Communications - Bit Parameters
Parameter
Modbus
Parameter No.
Notes
Alarm 2 Status
Alarm 3 Status
3
RO
1 = Active, 0 = Inactive
RO
1 = Alarm 1 Latched, 0 = Not Latched*
RO
1 = PV Under-range, 0 = PV within range
PV Over Range
6
RO
7
RO
1 = Sensor Break Active, 0 = Sensor Break Inactive
8
Writing any value resets all latched alarm relays.
Note: Outputs will only reset if their alarm condition
is no longer present.
9
Writing any value resets the stored maximum displayed
PV value
Reset Minimum PV
10
WO
Alarm 1 Status
1
RO
1 = Active, 0 = Inactive
2
RO
1 = Active, 0 = Inactive
Alarm 1 Latched
4
PV Under Range
5
1 = PV Over-range, 0 = PV within range
Sensor Break
Latched Alarm
Reset
WO
Writing any value resets the stored minimum displayed
PV value
Reset Elapsed
Time
11
WO
Writing any value resets the stored alarm 1 active time
value
Alarm 5 Status
12
RO
1 = Active, 0 = Inactive
Alarm 5 Status
13
RO
1 = Active, 0 = Inactive
Alarm 2 Latched
14
RO
1 = Alarm 2 Latched, 0 = Not Latched*
Alarm 3 Latched
15
RO
1 = Alarm 3 Latched, 0 = Not Latched*
Alarm 4 Latched
17
1 = Alarm 5 Latched, 0 = Not Latched*
To set the bit value to 1 write FF, to set the bit value to 0 write 00. Refer to Function Code 05 in the
Modbus Communications section
Alarm Latched status requests always returns 0 if that alarm is not configured to be
latching.
16
RO
1 = Alarm 4 Latched, 0 = Not Latched*
Alarm 5 Latched
Page 114
P6010 & P8010 Model Group
59305, Issue 6 – March 2006