Pid m – IDEC MicroSmart Pentra User Manual
Page 85
C
ONFIGURING
PID M
ODULE USING
W
IND
LDR
6-20
FC5A MicroSmart PID Module User’s Manual FC9Y-B1283
Offset from
the control
register
Parameter
Description
R/W
CH0
CH1
(7)
+186
+396
ARW (Anti-Reset Windup)
0 to 100%
R/W
(8)
+187
+397
Output Manipulated
Variable Rate-of-Change
0 to 100%/sec
R/W
(9)
+188
+398
Alarm 1 Value
Refer to the valid range for alarm 1 to alarm 8 values
shown in the following table.
R/W
(10)
+189
+399
Alarm 2 Value
(11)
+190
+400
Alarm 3 Value
(12)
+191
+401
Alarm 4 Value
(13)
+192
+402
Alarm 5 Value
(14)
+193
+403
Alarm 6 Value
(15)
+194
+404
Alarm 7 Value
(16)
+195
+405
Alarm 8 Value
(17)
+197
+407
Output Manipulated
Variable Upper Limit
When output type is voltage:
Output manipulated variable lower limit to 100%
When output type is current:
Output manipulated variable lower limit to 105%
R/W
(18)
+198
+408
Output Manipulated
Variable Lower Limit
When output type is voltage:
0% to output manipulated variable upper limit
When output type is current:
-5% to output manipulated variable upper limit
R/W
(19)
+199
–
Cooling Proportional
Band
0.0 to 10.0 times
(Cooling proportional band is the multiplication of
heating proportional band)
R/W
(20)
+200
–
Overlap/Dead Band
When input range unit is Celsius:
-200.0 to 200.0°C
When input range unit is Fahrenheit:
-200.0 to 200.0°F
When input is voltage or current:
-2000 to 2000
R/W
Valid Range for Alarm 1 to Alarm 8 Value
*1: When input is voltage/current, full scale is the linear conversion span.
*2: When input is voltage/current, the valid range is the linear conversion minimum value to linear conversion maximum
value.
Alarm Type
Valid Range
Upper Limit Alarm
–(Full scale) to full scale *1
Lower Limit Alarm
–(Full scale) to full scale *1
Upper/Lower Limits Alarm
0 to full scale *1
Upper/Lower Limit Range Alarm
0 to full scale *1
Process High Alarm
Input range lower limit to input range upper limit *2
Process Low Alarm
Input range lower limit to input range upper limit *2
Upper Limit Alarm with Standby
–(Full scale) to full scale *1
Lower Limit Alarm with Standby
–(Full scale) to full scale *1
Upper/Lower Limits Alarm with Standby
0 to full scale *1