Pid m – IDEC MicroSmart Pentra User Manual
Page 74
C
ONFIGURING
PID M
ODULE USING
W
IND
LDR
F
C5A MicroSmart PID Module User’s Manual FC9Y-B1283
6-9
Offset from
the control
register
Parameter
Description
R/W
CH0
CH1
(7)
+60
+137
Set Point (SP) Lower Limit/
Linear Conversion
Minimum Value
When input is thermocouple/resistance thermometer:
Input range lower limit to set point (SP) upper limit
When input is voltage/current:
Input range lower limit to linear conversion maximum
R/W
(8)
+62
+139
PV Correction
When input range unit is Celsius:
-100.0 to 100.0°C
When input range unit is Fahrenheit:
-100.0 to 100.0°F
When input is voltage/current:
-1000 to 1000
R/W
(9)
+63
+140
PV Filter Time Constant
0.0 to 10.0 sec
R/W
(10)
+65
+142
Alarm 1 Type
0: No alarm action
1: Upper limit alarm
2: Lower limit alarm
3: Upper/Lower limits alarm
4: Upper/Lower limit range alarm
5: Process high alarm
6: Process low alarm
7: Upper limit alarm with standby
8: Lower limit alarm with standby
9: Upper/Lower limits alarm with standby
R/W
+66
+143
Alarm 2 Type
+67
+144
Alarm 3 Type
+68
+145
Alarm 4 Type
+69
+146
Alarm 5 Type
+70
+147
Alarm 6 Type
+71
+148
Alarm 7 Type
+72
+149
Alarm 8 Type
(11)
+37
+114
Alarm 1 Value
See page 6-10 for the detail about alarm value range.
R/W
+38
+115
Alarm 2 Value
+39
+116
Alarm 3 Value
+40
+117
Alarm 4 Value
+41
+118
Alarm 5 Value
+42
+119
Alarm 6 Value
+43
+120
Alarm 7 Value
+44
+121
Alarm 8 Value
(12)
+73
+150
Alarm 1 Hysteresis
When the unit is Celsius:
0.1 to 100.0°C
When the unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage/current:
1 to 1000
R/W
+74
+151
Alarm 2 Hysteresis
+75
+152
Alarm 3 Hysteresis
+76
+153
Alarm 4 Hysteresis
+77
+154
Alarm 5 Hysteresis
+78
+155
Alarm 6 Hysteresis
+79
+156
Alarm 7 Hysteresis
+80
+157
Alarm 8 Hysteresis
(13)
+81
+158
Alarm 1 Delay Time
0 to 10000 sec
R/W
+82
+159
Alarm 2 Delay Time
+83
+160
Alarm 3 Delay Time
+84
+161
Alarm 4 Delay Time
+85
+162
Alarm 5 Delay Time
+86
+163
Alarm 6 Delay Time
+87
+164
Alarm 7 Delay Time
+88
+165
Alarm 8 Delay Time