Pid m – IDEC MicroSmart Pentra User Manual
Page 76
C
ONFIGURING
PID M
ODULE USING
W
IND
LDR
F
C5A MicroSmart PID Module User’s Manual FC9Y-B1283
6-11
Input Parameters List when External SP Input is Selected
Control Registers
Offset from
the control
register
Parameter
Description
R/W
(1)
+55
Input Range
(External SP input)
0: Disabled (Note)
1: 4 to 20mA DC
2: 0 to 20mA DC
3: 1 to 5V DC
4: 0 to 1V DC
5: Cascade control (Note)
Note: Disabled and Cascade control cannot be selected
in the input range.
R/W
(2)
+139
PV Correction
-1000 to 1000
R/W
(3)
+140
PV Filter Time Constant
0.0 to 10.0 sec
R/W
(4)
+178
External SP Input Linear
Conversion Maximum
Value
External SP Input linear conversion min. to input range
upper limit of CH0
R/W
(5)
+179
External SP Input Linear
Conversion Minimum
Value
Input range lower limit of CH0 to external SP input linear
conversion max.
R/W
(6)
+177
External SP Input Bias
±20% of the external SP input linear conversion span
R/W
(7)
+142
Alarm 1 Type
0: No alarm action
1: No alarm action
2: No alarm action
3: No alarm action
4: No alarm action
5: Process high alarm
6: Process low alarm
7: No alarm action
8: No alarm action
9: No alarm action
R/W
+143
Alarm 2 Type
+144
Alarm 3 Type
+145
Alarm 4 Type
+146
Alarm 5 Type
+147
Alarm 6 Type
+148
Alarm 7 Type
+149
Alarm 8 Type
(8)
+114
Alarm 1 Value
See page 6-10 for the detail about alarm value range.
R/W
+115
Alarm 2 Value
+116
Alarm 3 Value
+117
Alarm 4 Value
+118
Alarm 5 Value
+119
Alarm 6 Value
+120
Alarm 7 Value
+121
Alarm 8 Value
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)