IDEC MicroSmart Pentra User Manual
Page 133

A
PPLICATION
E
XAMPLES
7-12
FC5A MicroSmart PID Module User’s Manual FC9Y-B1283
5. Program CH0 Parameters
Configure the Program CH0 parameters in the PID Module Configuration dialog box. To open Input
CH1 Parameters in the PID Module Configuration dialog box, click on Program (CH0) tab.
PID Module Configuration Dialog Box (Program CH0 Parameters)
Item
Setting
Step 0
Step 1
Step 2
Step 3
(1)
Set Point (SP)
100°C
100°C
800°C
800°C
(2)
Step Time
60 minutes
60 minutes
300 minutes
30 minutes
(3)
Wait Value
10°C
0°C
10°C
0°C
(4)
Alarm 1 Value
0°C
10°C
0°C
10°C
Notes:
• When the wait value is 0°C, the wait function is disabled.
• When the alarm value is 0°C, the alarm function is disabled.
• When a parameter for the program control except step time is changed in WindLDR, the parameter is
automatically copied to the following steps.
6. CH1 Parameters Setting
Configure CH1 Parameters in the same way as CH0.
7. Saving Parameters
Click OK button to save the configured parameters.
(1)
(2)
(3)
(4)