Pid m – IDEC MicroSmart Pentra User Manual
Page 80
C
ONFIGURING
PID M
ODULE USING
W
IND
LDR
F
C5A MicroSmart PID Module User’s Manual FC9Y-B1283
6-15
Offset from
the control
register
Parameter
Setting Range
R/W
CH0
CH1
(14)
+32
+109
Output Manipulated
Variable Rate-of-Change
0 to 100%/sec
R/W
(15)
+61
+138
Output ON/OFF
Hysteresis
When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage or current:
1 to 1000
R/W
(16)
+21
+24
Manual Mode Output
Manipulated Variable
When heating/cooling control is disabled:
Output manipulated variable lower limit to output
manipulated variable upper limit
When heating/cooling control is enabled:
- Cooling output manipulated variable upper limit to
heating output manipulated variable upper limit
R/W
(17)
+35
+112
Loop Break Alarm (LA)
Time
0 to 200 minutes
R/W
(18)
+36
+113
Loop Break Alarm (LA)
Span
When input range unit is Celsius:
0 to 150 °C
(Range with a decimal point: 0.0 to 150.0°C)
When input range unit is Fahrenheit:
0 to 150 °F
(Range with a decimal point: 0.0 to 150.0°F)
When input is voltage or current:
0 to 1500
R/W
(19)
+95
–
Cooling Method
0: Air cooling
1: Oil cooling
2: Water cooling
R/W
(20)
+48
–
Cooling Proportional
Band
0.0 to 10.0 times
(Cooling proportional band is the product of this value
and the heating proportional band)
R/W
(21)
+98
–
Cooling Output ON/OFF
Hysteresis
When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage or current:
1 to 1000
R/W
(22)
+50
–
Overlap/Dead Band
When input range unit is Celsius:
-200.0 to 200.0°C
When input range unit is Fahrenheit:
-200.0 to 200.0°F
When input is voltage or current:
-2000 to 2000
R/W
(23)
+91
+168
Program Control Mode
Start Type
0: PV start
1: PVR start
2: SP start
R/W
(24)
+96
+173
Set Point (SP) when
Program Control Starts
When input is thermocouple/resistance thermometer:
Set point (SP) lower limit to set point (SP) upper limit
When input is voltage or current:
Linear conversion min. to linear conversion max.
R/W
(25)
+92
+169
Step Time Unit
0: Minute
1: Second
R/W
(26)
+93
+170
Program End Action
0: Terminate program control
1: Continue program control (Repeat)
2: Hold program control
R/W
(27)
+97
+174
Number of Repeats
0 to 10000 times
R/W