Pid m – IDEC MicroSmart Pentra User Manual
Page 80

C
ONFIGURING
PID M
ODULE USING
W
IND
LDR
F
C5A MicroSmart PID Module User’s Manual FC9Y-B1283
6-15
Offset from
the control
register
Parameter
Setting Range
R/W
CH0
CH1
(14)
+32
+109
Output Manipulated 
Variable Rate-of-Change 
0 to 100%/sec
R/W
(15)
+61
+138
Output ON/OFF 
Hysteresis 
When input range unit is Celsius: 
 0.1 to 100.0°C 
When input range unit is Fahrenheit: 
 0.1 to 100.0°F 
When input is voltage or current: 
 1 to 1000 
R/W
(16)
+21
+24
Manual Mode Output 
Manipulated Variable 
When heating/cooling control is disabled: 
 Output manipulated variable lower limit to output 
manipulated variable upper limit
When heating/cooling control is enabled:
- Cooling output manipulated variable upper limit to 
heating output manipulated variable upper limit 
R/W
(17)
+35
+112
Loop Break Alarm (LA) 
Time 
0 to 200 minutes
R/W
(18)
+36
+113
Loop Break Alarm (LA) 
Span 
When input range unit is Celsius: 
 0 to 150 °C 
 (Range with a decimal point: 0.0 to 150.0°C) 
When input range unit is Fahrenheit: 
 0 to 150 °F 
 (Range with a decimal point: 0.0 to 150.0°F) 
When input is voltage or current: 
 0 to 1500 
R/W
(19)
+95
–
Cooling Method
0: Air cooling 
1: Oil cooling 
2: Water cooling 
R/W
(20)
+48
–
Cooling Proportional 
Band 
0.0 to 10.0 times 
(Cooling proportional band is the product of this value 
and the heating proportional band) 
R/W
(21)
+98
–
Cooling Output ON/OFF 
Hysteresis 
When input range unit is Celsius: 
 0.1 to 100.0°C 
When input range unit is Fahrenheit: 
 0.1 to 100.0°F 
When input is voltage or current: 
 1 to 1000 
R/W
(22)
+50
–
Overlap/Dead Band
When input range unit is Celsius: 
 -200.0 to 200.0°C 
When input range unit is Fahrenheit: 
 -200.0 to 200.0°F 
When input is voltage or current: 
 -2000 to 2000 
R/W
(23)
+91
+168
Program Control Mode 
Start Type 
0: PV start 
1: PVR start 
2: SP start 
R/W
(24)
+96
+173
Set Point (SP) when 
Program Control Starts 
When input is thermocouple/resistance thermometer:
Set point (SP) lower limit to set point (SP) upper limit
When input is voltage or current:
Linear conversion min. to linear conversion max.
R/W
(25)
+92
+169
Step Time Unit
0: Minute 
1: Second 
R/W
(26)
+93
+170
Program End Action
0: Terminate program control 
1: Continue program control (Repeat) 
2: Hold program control 
R/W
(27)
+97
+174
Number of Repeats
0 to 10000 times
R/W