IDEC MicroSmart Pentra User Manual
Page 61
D
EVICE
A
LLOCATION OF
PID
M
ODULE
5-20
FC5A MicroS
mart PID Module User’s Manual FC9Y-B1283
+73
+150
Alarm 1 Hysteresis
When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage or current input:
1 to 1000
R/W
+74
+151
Alarm 2 Hysteresis
R/W
+75
+152
Alarm 3 Hysteresis
R/W
+76
+153
Alarm 4 Hysteresis
R/W
+77
+154
Alarm 5 Hysteresis
R/W
+78
+155
Alarm 6 Hysteresis
R/W
+79
+156
Alarm 7 Hysteresis
R/W
+80
+157
Alarm 8 Hysteresis
R/W
+81
+158
Alarm 1 Delay Time
0 to 10000 sec
R/W
+82
+159
Alarm 2 Delay Time
R/W
+83
+160
Alarm 3 Delay Time
R/W
+84
+161
Alarm 4 Delay Time
R/W
+85
+162
Alarm 5 Delay Time
R/W
+86
+163
Alarm 6 Delay Time
R/W
+87
+164
Alarm 7 Delay Time
R/W
+88
+165
Alarm 8 Delay Time
R/W
+89
+166
AT Bias
When input range unit is Celsius:
0 to 50 °C (0.0 to 50.0°C for input with decimal point)
When input range unit is Fahrenheit:
0 to 100 °F (0.0 to 100.0°F for input with decimal point)
R/W
+90
+167
Control Mode
0: Fixed value control mode
1: Program control mode
R/W
+91
+168
Program Control Mode Start
Type
0: PV start
1: PVR start
2: SP start
R/W
+92
+169
Step Time Unit
0: Minute
1: Second
R/W
+93
+170
Program End Action
0: Terminate program control
1: Continue program control (Repeat)
2: Hold program control
R/W
+94
+171
Proportional Term
0: Proportional band
1: Proportional gain
R/W
+95
+172
Cooling Method
(CH0 only)
0: Air cooling
1: Oil cooling
2: Water cooling
R/W
+96
+173
Set Point (SP) when Program
Control Starts
When input is thermocouple or resistance thermometer:
Set point (SP) lower limit to set point (SP) upper limit
When input is voltage or current input:
Linear conversion min. to linear conversion max.
R/W
+97
+174
Number of Repeats
0 to 10000 times
R/W
+98
+175
Cooling Output ON/OFF
Hysteresis
(CH0 only)
When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage or current input:
1 to 1000
R/W
+99
+176
Output Type
(FC5A-F2M2 only)
0: Non-contact voltage output (for SSR drive)
1: Current output
R/W
+100
+177
External SP Input Bias
(CH1 only)
±20% of the external SP input linear conversion span
R/W
+101
+178
External SP Input Linear
Conversion Maximum Value
(CH1 only)
External SP input Linear conversion min. to input range
upper limit
R/W
+102
+179
External SP Input Linear
Conversion Minimum Value
(CH1 only)
Input range lower limit to external SP input linear conversion
max.
R/W