FC5A MicroSmart PID Module User’s Manual FC9Y-B1283
1: Enable
(4)
+20
+23
Set Point (SP)
When input is thermocouple/resistance thermometer:
Set point (SP) lower limit to set point (SP) upper limit
When input is voltage/current:
Linear conversion min. to linear conversion max.
R/W
(5)
+94
+171
Proportional Term
0: Proportional band
1: Proportional gain
R/W
(6)
+26
+103
Proportional Band/
Proportional Gain
Proportional band:
When input range unit is Celsius:
0 to 10000°C
(Range with a decimal point: 0.0 to 1000.0°C)
When input range unit is Fahrenheit:
0 to 10000°F
(Range with a decimal point: 0.0 to 1000.0°F)
When input is voltage/current:
0.0 to 1000.0%
Proportional gain:
0.00 to 100.00%
R/W
(7)
+27
+104
Integral Time
0 to 10000 sec
R/W
(8)
+28
+105
Derivative Time
0 to 10000 sec
R/W
(9)
+29
+106
ARW (Anti-Reset Windup)
0 to 100%
R/W
(10)
+89
+166
AT Bias
When input range unit is Celsius:
0 to 50 °C
(Range with a decimal point: 0.0 to 50 . 0 °C)
When input range unit is Fahrenheit:
0 to 100 °F
(Range with a decimal point: 0.0 to 100 . 0 °F)
R/W
(11)
+31
+108
Reset
When input range unit is Celsius:
-100.0 to 100.0 °C
When input range unit is Fahrenheit:
-100.0 to 100.0 °F
When input is voltage or current:
-1000 to 1000
R/W
(12)
+33
+110
Set Point (SP) Rise Rate
When input range unit is Celsius:
0 to 10000°C/min
(Range with a decimal point: 0.0 to 1000.0°C/min)
When input range unit is Fahrenheit:
0 to 10000°F/min
(Range with a decimal point: 0.0 to 1000.0°F/min)
When input is voltage or current:
0 to 10000/min
R/W
(13)
+34
+111
Set Point (SP) Fall Rate
When input range unit is Celsius:
0 to 10000°C/min
(Range with a decimal point: 0.0 to 1000.0°C/min)
When input range unit is Fahrenheit:
0 to 10000°F/min
(Range with a decimal point: 0.0 to 1000.0°F/min)
When input is voltage or current:
0 to 10000/min
R/W