Pid m – IDEC MicroSmart Pentra User Manual
Page 82
C
ONFIGURING
PID M
ODULE USING
W
IND
LDR
F
C5A MicroSmart PID Module User’s Manual FC9Y-B1283
6-17
PID Module Configuration - Output Parameters List (CH0 and CH1)
The output parameters for CH0 and CH1 are described here.
Output Parameters when Heating/Cooling Control is Enabled
Control Registers
Offset from
the control
register
Parameter
Description
R/W
CH0
CH1
(1)
+99
+176
Output Type
0: Non-contact voltage output (for SSR drive)
1: Current output
R/W
(2)
+30
+107
Control Period
1 to 120 sec
R/W
(3)
+46
+123
Output Manipulated
Variable Upper Limit
When output type is voltage:
Output manipulated variable lower limit to 100%
When output type is current:
Output manipulated variable lower limit to 105%
R/W
(4)
+47
+124
Output Manipulated
Variable Lower Limit
When output type is voltage:
0% to output manipulated variable upper limit
When output type is current:
-5% to output manipulated variable upper limit
R/W
(5)
+49
–
Cooling Control Period
1 to 120 sec
R/W