10�6 pm – Solare Datensysteme Solar-Log User Manual
Page 41

41
Connector Assignments and Wiring
10�6 PM+
The Solar-Log™ PM+ models come with a 6-pin PM+ interface on the top side of the Solar-Log
TM
.
The interface has been designed to link the ripple control receivers or telecontrol plants with potential-free
signal contacts. Up to two ripple control receivers can be connected. This allows the commands from grid
operators for active and reactive power to be interpreted.
Fig.: 6-pin PM+ interface
Fig.: 6-pin Terminal block connector
PM+
PIN
Assignment
Description
1
+5V
Control voltage for active
power control
2
D_IN_1
Control input 1
3
D_In_2
Control input 2
4
D_In_3
Control input 3
5
D_In_4
Control input 4
6
+5V
Control voltage for reactive
power reduction
To provide the highest possible flexibility, the individual active and reactive power values can be assigned
to inputs D_IN_1 to D_IN_4
for more information