29�3�1 portal transfer fault messages, 29�3�2 fault messages feed-in management – Solare Datensysteme Solar-Log User Manual
Page 211

211
Faults
29�3�1 Portal Transfer Fault messages
Portal Transfer Fault messages
Error code
Message
Possible cause/remedy
101
The server address could
not be resolved.
The access type was not configured. An
alternative DNS server is required. The wrong
server was entered. The network connection
was disconnected and could not be reestab-
lished.
102
Cannot open socket.
Possible causes: Unknown. If this error contin-
ues to occur, contact our technical support.
103
Cannot connect to socket.
Possible causes: The connection is blocked by
a firewall or a router. The wrong server was
entered. The server is offline.
104 and 106
Connection error.
This can occasionally happen with GPRS con-
nections. Try it again. The network cable has
a loose connection. There are problems with
your Internet connection.
220
Authentication failure
(portal).
The portal registration was done incorrectly.
The portal was not configured for HTTP
transfers. The wrong server was entered.
222
Connection to server
successful but no answer
received to the inquiry.
Check the entered portal server name.
This can happen occasionally to GPRS con-
nections. Simply try again.
Other
General errors.
There is detailed description of this error.
If this error continues to occur, contact our
technical support.
.
29�3�2 Fault messages Feed-in Management
These fault messages are displayed on the LCD display.
The percentage symbol blinks and the corresponding error code is displayed.
Fault messages
Feed-in Management
Error code
Possible cause/remedy
1
Undefined status for the PM+ interface or an invalid channel setting
for the active and reactive power management.
=> Check the wiring and configuration.
2
Communication error with the I/O Box
=> Check the wiring and the power supply for the I/O Box.
=> Check the interface selected under Configuration | Special Func-
tions | Feed-in Management | Profile.