20�4 alarm, Only solar-log 1000 and 2000) – Solare Datensysteme Solar-Log User Manual
Page 111

111
Configuring Notifications
20�4 Alarm
(only Solar-Log 1000 and 2000)
The Solar-Log™ continuously monitors its internal alarm contact. If this contact is opened, it sets off an
alarm which can be indicated in various ways. In the
Alarm
tab, the alarm contact can be activated and
different types of notification can be configured.
Activating alarm contact
Procedure:
•
Select
Configuration | Plant | Plant groups
from the menu.
•
Activate the
Activate Alarm Contact
button.
•
SAVE
settings.
After activating alarm notifications, a triggered alarm can be indicated by:
•
•
Text message (SMS)
•
Relay
•
Speaker
.
The e-mail and text message (SMS) settings must be pre-configured.
Procedure
•
Activate
the desired
Notifications
.
•
SAVE
settings.
Test section
Here you have the option to perform an alarm test.
20�5 Power & Failure
Performance monitoring is based on a comparison of the power out from all of the inverters, including
individual trackers in the case of inverters with more than one tracker or, as the case may be, sensors. If
the target power deviates from the actual power by more than a certain tolerance (= min. feed-in power),
a notification can be sent by e-mail and/or text message (SMS) after the selected fault duration has been
reached.
If an individual module loses power, the string power for the same level of irradiation will drop, and can
thus be detected and reported.
Power comparison always works reliably, even if the weather is cloudy. The important thing is that all mod-
ules should not be overshadowed. Therefore, the monitoring period should be scheduled for periods when
there are no shadows.
As power measurement in the inverter is very inaccurate under a certain threshold, a minimum percentage
value can also be specified below which monitoring is interrupted.
Procedure
•
Select the device that is to be monitored
•
Select the Performance Monitoring mode.
Select per MPP tracker or for the total of all of the MPP trackers. There is also the option to deacti-
vate the performance monitoring.
•
Set the monitoring parameters
•
Enter the monitoring begin