32�5 Digital Interfaces
Solar-Log™provides two interfaces for exporting the current data.
The data is updated every 15-60 seconds.
WARNING
The following descriptions for two interfaces are intended for users with a tech-
nical background. Solare Datensysteme provides these interfaces without any
guarantee and with the exclusion of any legal liability.
We do not offer any telephone support for these two interfaces.
Wikipedia is a source for general information:
32�5�1 Modbus TCP
The software interface function allows external systems to have access to internal data on the Solar-Log
™. The interface has been designed so that live data can be retrieved. The function is available for every
Solar-Log™ with the current firmware version.
The interface cannot be used to configure the Solar-Log ™ and the devices connected to it. The entire con-
figuration is carried out via the Solar-Log ™ Internet browser interface.
Modbus TCP Port: 502
Slave ID: 1
Implementing Modbus functions:
Read 04 or several 16 bit words
Modbus Data and Register
Data point
Unit
Value
range
Address Number
Reg�
Func
Codec
Description
lastUpdateTime
Sec
32bit un-
signed
3.500
2
04
Unix time, when the last register update
occurred. 0=still no live data
Pac
W
32 bit un-
signed
3.502
2
04
Total output P
AC
from all of the inverters and
meters in inverter mode
Pdc
W
32 bit un-
signed
3.504
2
04
Total output P
DC
from all inverters
Uac
V
16 bit un-
signed
3.506
1
04
Average voltage U
AC
from the inverter
DC voltage:
V
16 bit un-
signed
3.507
1
04
Average voltage U
DC
from the inverter
Daily yield
Wh
32 bit un-
signed
3.508
2
04
Total yield for the day from all of the invert-
ers
Yesterday yield
Wh
32 bit un-
signed
3.510
2
04
Total yield for the previous day from all of
the inverters
Monthly yield
Wh
32 bit un-
signed
3.512
2
04
Total yield for the month from all of the
inverters