En 11 shutdown/disassembly, 1 shutting down the inverter, 2 uninstalling the inverter – KACO Powador 30.0 - 60.0 TL3 User Manual
Page 54: 3 dismantling the inverter

Shutdown/Disassembly
Page 54
Operating Instructions for Powador 30.0-72.0 TL3_EN
EN
EN
11 Shutdown/Disassembly
11.1
Shutting down the inverter
DANGER
Lethal voltages are still present in the terminals and cables of the inverter even after the
inverter has been switched off and disconnected.
Severe injuries or death result if the cables and terminals in the inverter are touched.
›
After shutdown, wait at least fi ve minutes before working on the inverter.
DANGER
Destruction of the DC plug
The DC plug may be destroyed by arcing if it is disconnected under load.
›
It is essential that the shutdown sequence is carried out in the correct order.
Shutdown sequence
1. Switch
off the grid voltage by turning off the external circuit breakers.
2. Disconnect the PV generator using the DC isolator switches.
DANGER! The DC cables are still live.
Ensure that there is no voltage present on the grid connection terminals.
11.2
Uninstalling the inverter
↻ Shut down the inverter.
1.
Unlock and open the housing door.
2. Open the connection cover connection area.
3. Remove the interface cable.
4. Release the DC and AC cables from the connection terminals.
5. Open the cable fi ttings.
6. Pull out the cables.
»
The uninstallation of the inverter is complete. Continue with dismantling.
11.3
Dismantling the inverter
CAUTION
Risk of injury if the inverter tips over!
Risk of tipping due to high centre of gravity, particularly with the door open.
›
Secure the inverter to prevent tipping before disassembly.
›
Close and lock the doors of the inverter.
›
Only then remove the wall and fl oor fastenings.
↻ Shut down the inverter.
↻ Uninstall the inverter.
1.
Remove the inverter fastening.
2. Securely pack up the inverter if it is to be used later
or
have the inverter disposed of professionally.