"Parameters" menu
Press the right arrow button or the OK button.
NOTE: The inverter does not display the "Parameters"
menu in the standard confi guration. To display the
Parameters menu:
1.
Open the menu.
2. Simultaneously hold down the up and down but-
tons for several seconds.
4
1
2
3
1
Country
1.
Enter the four-digit password using the 4-way
button. The password is unit-specifi c.
2. Confi rm the entry with the OK button.
3. Set the desired country setting.
NOTE: This option infl uences the country-specifi c
operating settings of the inverter. Please consult KACO
service for further information.
4
1
2
3
1
Grid type/guide-
line
Select the grid type for the inverter’s installation
location.
AU, BG, FR,
GR, PT, ES,
CZ, KR
4
1
2
3
1
Switch-off volt.
The inverter is equipped with redundant 3-phase moni-
toring. If the grid frequency exceeds or drops below the
confi gured values, the inverter switches off . The mini-
mum switch-off threshold can be set in 1 V increments.
Confi gure the switch-off values for undervoltage
and overvoltage.
Where necessary, set period from occurrence of the
fault to shutdown of the inverter.
DE, AU, BG,
FR, GR, HU,
IL, PT, ES, CZ,
KR
4
1
2
3
1
Switch-off freq.
The inverter continuously monitors the grid frequency. If
the grid frequency exceeds or drops below the confi g-
ured values, the inverter switches off .
Set limit values for underfrequency
and overfrequency in 0.1 Hz increments.
Set period from occurrence of the fault to shutdown
of the inverter.
DE-NSp, BE,
FR, IT, AT, PL,
UD
4
1
2
3
1
Overvoltage shutd.
Activate or deactivate password protection.
Specify the shutdown threshold
for overvoltage shutdown.
The 10-minute average for the measured voltage as
per EN50160 is used.
Set period from occurrence of the fault to shutdown
of the inverter.
DE-MSp, FR,
GB59/3, HU,
IL, IN, IT, AT,
PL, RU, ES,
TH, ZA, UD
Specify the shutdown threshold
for fast and slow overvoltage shutdown.
Set period from occurrence of the fault to shutdown
of the inverter.
AT, GB, JO
0
1
2
3
1
Protection param-
eters
Display of 2-phase protection parameters.
To show the protection parameters, select the “Dis-
play” key.