Configuration and Operation

Page 38

Operating Instructions for Powador 30.0-72.0 TL3_EN

EN

EN

Coun-

try-spec.

setting

menu

level

Display/

setting

Action in this menu/meaning

4

1

2

3

4

"Parameters" menu

 Press the right arrow button or the OK button.

NOTE: The inverter does not display the "Parameters"
menu in the standard confi guration. To display the
Parameters menu:

1.

Open the menu.

2. Simultaneously hold down the up and down but-

tons for several seconds.

4

1

2

3

1

Country

1.

Enter the four-digit password using the 4-way
button. The password is unit-specifi c.

2. Confi rm the entry with the OK button.

3. Set the desired country setting.

NOTE: This option infl uences the country-specifi c
operating settings of the inverter. Please consult KACO
service for further information.

4

1

2

3

1

Grid type/guide-

line

 Select the grid type for the inverter’s installation

location.

AU, BG, FR,

GR, PT, ES,

CZ, KR

4

1

2

3

1

Switch-off volt.

The inverter is equipped with redundant 3-phase moni-
toring. If the grid frequency exceeds or drops below the
confi gured values, the inverter switches off . The mini-
mum switch-off threshold can be set in 1 V increments.

 Confi gure the switch-off values for undervoltage

and overvoltage.

 Where necessary, set period from occurrence of the

fault to shutdown of the inverter.

DE, AU, BG,

FR, GR, HU,

IL, PT, ES, CZ,

KR

4

1

2

3

1

Switch-off freq.

The inverter continuously monitors the grid frequency. If
the grid frequency exceeds or drops below the confi g-
ured values, the inverter switches off .

 Set limit values for underfrequency

and overfrequency in 0.1 Hz increments.

 Set period from occurrence of the fault to shutdown

of the inverter.

DE-NSp, BE,

FR, IT, AT, PL,

UD

4

1

2

3

1

Overvoltage shutd.

 Activate or deactivate password protection.

 Specify the shutdown threshold

for overvoltage shutdown.
The 10-minute average for the measured voltage as
per EN50160 is used.

 Set period from occurrence of the fault to shutdown

of the inverter.

DE-MSp, FR,

GB59/3, HU,

IL, IN, IT, AT,

PL, RU, ES,

TH, ZA, UD

 Specify the shutdown threshold

for fast and slow overvoltage shutdown.

 Set period from occurrence of the fault to shutdown

of the inverter.

AT, GB, JO

0

1

2

3

1

Protection param-

eters

Display of 2-phase protection parameters.

 To show the protection parameters, select the “Dis-

play” key.