Maintenance/Troubleshooting

Page 50

Operating Instructions for Powador 30.0-72.0 TL3_EN

EN

EN

E = The indicated work may only be carried out by an authorised electrician.

K = The indicated work may only be carried out by a service employee of KACO new energy GmbH!

Status

Display

Explanation

Action

OS 1

Waiting for
feed-in

Self-test: The grid parameters and gen-
erator voltage are being checked.

-

-

OS 2

Generator volt-
age
too low

Insuffi

cient generator voltage and

power,

status before the transition to night
shutdown

-

-

OS 8

Self-test

Checks the shutdown of the power
electronics as well as the grid relay
before feed-in mode.

-

-

FS

10

Temperature in

unit too high

In case of overheating, the inverter
switches off . Possible causes:

Ambient temperature too high,

Fans covered,

Inverter defective.

 Uncover the fans.

 Notify your author-

ised electrician.

B

B
E

OS 11

Measured values

Power limitation: If the generator power is too high, the inverter limits
itself to the maximum power (e.g. around noon if the generator capacity
is too large).

FS

17

Shutting down
Powador-protect

The activated grid and system protec-
tion has been tripped.

 Wait for reactivation.

 Notify your author-

ised electrician if the
fault occurs several
times.

E

FS

18

Resid. current
shutdown

Residual current was detected. The
feed-in was interrupted.

 Notify your author-

ised electrician.

E

FS

19

Generator insu-
lation
fault

There is an insulation fault on the PV
generator. The feed-in was interrupted.

 Notify your author-

ised electrician if the
fault occurs several
times.

E

FS

30

Fault

Transformer fault

The current and voltage measure-
ments in the inverter are not within
acceptable range.

-

-

FS

32

Fault

Self-test

The internal grid separation relay test
has failed.

 Notify your author-

ised electrician if the
fault occurs several
times.

E

FS

33

Fault

DC feed-in

The DC feed-in has exceeded the per-
mitted value. This DC feed-in can be
caused by grid conditions and may not
necessarily indicate a fault.

 Notify your author-

ised electrician if the
fault occurs several
times.

E

FS

34

Internal commu-
nication error

A communication error has occurred in
the internal data transmission.

 Notify your author-

ised electrician.

E

 Check the data

cable.

Table 6:

Operating status and fault messages on the display