Maintenance/Troubleshooting

Operating Instructions for Powador 30.0-72.0 TL3_EN

Page 51

EN

Status

Display

Explanation

Action

FS

35

Protection shut-
down SW

Protective shutdown of the
software (AC overvoltage, AC overcur-
rent, DC link overvoltage, DC overvolt-
age, DC overtemperature).

Not a fault Grid-related
shutdown, the grid connects
again automatically.

FS

36

Protection shut-
down HW

Protective shutdown of the
hardware (AC overvoltage, AC overcur-
rent, DC link overvoltage).

Not a fault Grid-related
shutdown, the grid connects
again automatically.

FS

38

Generator over-
voltage error

The voltage of the DC generator is too
high. The PV generator is confi gured
incorrectly.

 Notify your author-

ised electrician.

E

FS

41-
46

Line failure:

undervoltage L1,
overvoltage L1,
undervoltage L2,
overvoltage L2,
undervoltage L3,
overvoltage L3

The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.

 Notify your author-

ised electrician.

E

FS

47

Grid failure
phase-to-phase
voltage

The measured line-to-line voltage is
outside of the tolerance limits.

FS

48

Line failure:

Underfrequency

Grid frequency is too low.
This fault may be grid-related.

 Notify your author-

ised electrician.

E

FS

49

Line failure:

Overfrequency

Grid frequency is too high.
This fault may be grid-related.

 Notify your author-

ised electrician.

E

FS

50

Line failure:

average voltage

The grid voltage measurement accord-
ing to EN 50160 has exceeded the
maximum permitted limit value.
This fault may be grid-related.

 Notify your author-

ised electrician.

E

FS

57

Waiting for

reactivation

Waiting time of the inverter after a
fault.

Inverter does not switch on
again until the country-specifi c
time has elapsed.

FS

58

Overtemperature

Control card

The temperature inside the unit was
too high. The inverter switches off to
prevent damage to the hardware.

 Provide for suffi

cient

ventilation.

E

FS

59

Self test error

A fault occurred during a self-test.

 Notify your author-

ised electrician.

E

OS 60

Generator
voltage too high

The inverter does not begin feeding
into the grid until the PV voltage falls
below a specifi ed value.

-

-

OS 61

External
limit (%)

The external limit Power control was activated by the grid operator. The
inverter limits its power.

OS 63

Measured values

P(f )/frequency-dependent power reduction: Frequency-dependent
power reduction will be activated when the BDEW (German Association
of Energy and Water Industries) Medium Voltage Directive goes into
eff ect. Power reduction starts at a frequency of 50.2 Hz.

OS 64

Measured values

Output current limiting: The AC current is limited once the specifi ed
maximum value has been reached.

Table 6:

Operating status and fault messages on the display