Maintenance/Troubleshooting

Page 48

Operating Instructions for Powador 30.0-72.0 TL3_EN

EN

EN

Fault

Cause of fault

Explanation/remedy

By

The grid fuse
trips.

The grid fuse
capacity is too low.

In cases of high solar radiation, the inverter exceeds its rated
current for a short period, depending on the PV generator.

 Select the capacity of the inverter’s pre-fuse to be some-

what higher than the maximum feed-in current (see the
“Installation” section).

E

 Contact the grid operator if the grid failure continues to

occur.

E

Damage to the
inverter’s hard-
ware.

If the grid fuse trips immediately when the inverter goes into
feed-in mode (after the start-up period is complete), the invert-
er’s hardware is probably damaged.

 Contact KACO Service to test the hardware.

E

The inverter dis-
plays an impos-
sible daily peak
value.

Faults in the grid.

The inverter continues to operate as normal without losses to
the yield, even when an erroneous daily peak value is displayed.
The value is reset overnight.

 To reset the value immediately, switch the inverter off by

disconnecting it from the grid and switching off the DC,
then switch it back on.

E

Daily yields do
not correspond to
the yields on the
feed-in meter.

Tolerances of
the measuring
elements in the
inverter.

The measuring elements of the inverter have been selected to
ensure maximum yields. Due to these tolerances, the daily yields
shown may deviate from the values on the feed-in meter by up
to 15%.

 No action

-

The inverter is
active but is not
feeding into the
grid. Display:
“Waiting for
feed-in”

Generator volt-
age too low

Grid voltage or
PV generator
voltage unsta-
ble.

The PV generator voltage or power is not suffi

cient for feed-in

(solar radiation is too low).

The inverter checks the grid parameters before the feed-in
process begins. The length of time it takes to switch back on
again diff ers from country to country, depending on applica-
ble standards and regulations, and may be several minutes.

The starting voltage may have been set incorrectly.

 Adjust starting voltage in the Parameter menu if required.

K

Table 5:

Troubleshooting

This manual is related to the following products: