6 starting up the inverter, 1 switching on the inverter, Danger – KACO Powador 30.0 - 60.0 TL3 User Manual
Page 29
Installing the inverter
Operating Instructions for Powador 30.0-72.0 TL3_EN
Page 29
EN
7.6
Starting up the inverter
DANGER
Lethal voltages are still present in the terminals and cables of the inverter even after the
inverter has been switched off and disconnected.
Severe injuries or death result if the cables and terminals in the inverter are touched.
Only appropriately qualifi ed and authorised electricians may start up the inverter.
FR
Attachment of safety label in accordance with UTE C 15-712-1
The code of practice UTE C 15-712-1 requires that, upon connec-
tion to the French low-voltage distribution network, a safety
sticker showing a warning to isolate both power sources when
working on the device must be attached to each inverter.
Attach the provided safety sticker visibly to the outside of
the inverter housing.
ATTENTION
Présence de deux
sources de tension
- Réseau de distribution
-Panneux photovoltaïques
Isoler les deux sources
avant toute intervention
7.6.1
Switching on the inverter
↻ The inverter has been mounted and electrically installed.
↻ The PV generator supplies a voltage above the confi gured start voltage.
1.
Connect the grid voltage using the external circuit breakers.
2. Connect the PV generator using DC isolator switch (0
→ 1).
»
The inverter begins to operate.
»
During the initial start-up: Follow the instructions of the New Connection Wizard.