KACO Powador 30.0 - 60.0 TL3 User Manual
Page 40
Configuration and Operation
Page 40
Operating Instructions for Powador 30.0-72.0 TL3_EN
EN
EN
Coun-
try-spec.
setting
menu
level
Display/
setting
Action in this menu/meaning
4
1
2
3
1
Power
limitation
The output power of the inverter can be set perma-
nently to a lower value than the maximum output
power by the internal power limiting. This may be nec-
essary in order to limit the maximum power rating of
the system at the grid connection point, upon the grid
operator's request.
The value can be protected from the very fi rst output
limitation entry. After setting a limitation, the value can
only be changed by entering a device-specifi c password.
1.
Activate password protection if necessary.
2. Specify the activation status.
3. Specify the limit value for maximum feed-in power.
4. Confi rm the entry with the OK button.
4
1
2
3
1
Powador-protect
Confi gures the support for grid shutdown by a Powador
protect connected to the digital input of the inverter.
↻ For Auto/On: A Powador protect is operating in
the photovoltaic system and is connected to the
inverter at the digital input/output.
Auto: The inverter automatically detects a Pow-
ador-protect integrated into the photovoltaic
system.
On: The digital signal of the Powador protect must
be present to the digital input of the inverter for the
inverter to start with feed-in.
Off : The inverter does not check whether a Pow-
ador-protect is integrated into the PV system.
4
1
2
3
1
Iso.resistor
Set threshold value (in 1 kOhm steps) at which the
insulation monitor reports a fault.
DE-MSp, FR,
AT, PL, RU,
ES, TH, ZA
4
1
2
3
1
Activate FRT
The inverter supports dynamic grid stabilisation (Fault
Ride-Through).
The following parameters can be set:
Operation mode
Dead band
Dead band mode
Constant k
Dynamic blind current
DE, CH, BE,
FR, GB, IL, IT,
AT, PL, RU, ES,
KR, TH, ZA
4
1
2
3
1
Reactive power
Open the menu: Press the right arrow button or the
OK button.
Activating idle power process: select process and
press OK. The active process is highlighted.
4
1
2
3
2
cos-phi specifi ca-
tion
Confi gure power factor.
If a power factor is selected which is not equal to
1: Select the type of phase shift (under-excited/
over-excited).
DE-MSp, FR,
GB, IL, IT, AT,
PL, RU, ES,
KR, TH
4
1
2
3
2
Q const.
Set the idle power Q (in %) to a fi xed value.
Select the type of phase shift (under-excited/
over-excited).