KACO Powador 30.0 - 60.0 TL3 User Manual
Page 52
Maintenance/Troubleshooting
Page 52
Operating Instructions for Powador 30.0-72.0 TL3_EN
EN
EN
Status
Display
Explanation
Action
FS
67
Fault
at power sec-
tion 1
There is a fault in the power section.
Notify your author-
ised electrician.
E
FS
70
Fan error
The fan is malfunctioning.
Replace
defective fan
E
FS
73
Standalone grid
err.
Standalone mode was detected.
-
-
OS 74
External idle
power require-
ment
The grid operator limits the feed-in
power of the inverter via the transmit-
ted reactive power factor.
-
-
OS 79
Insulation meas-
urement
PV generator’s insulation is being
measured
-
-
FS
80
Insulation meas.
not possible
The insulation measurement cannot
be performed because the generator
voltage is too volatile.
-
-
FS
81,
82,
83
Protection shut-
down line volt.
L1 L2, L3
Overvoltage has been detected on
a conductor. An internal protective
mechanism has disconnected the
device to protect it against damage.
In case of repeated
occurrence:
Notify your author-
ised electrician.
E
FS
84
Protection shut-
down undervolt.
DC link
A voltage deviation has been found
in the DC link. An internal protective
mechanism has disconnected the
device to protect it against damage.
In case of repeated
occurrence:
Notify your author-
ised electrician.
E
FS
85
Protection shut-
down overvolt.
DC link
E
FS
86
Protection shut-
down: DC link
asymmetry
Overvoltage has been found in the DC
link. An internal protective mechanism
has disconnected the device to protect
it against damage.
In case of repeated
occurrence:
Notify your author-
ised electrician.
E
FS
87,
88,
89
Protection shut-
down overcur-
rent
L1, L2, L3
A current that has been found on a
conductor is too high. An internal
protective mechanism has discon-
nected the device to protect it against
damage.
In case of repeated
occurrence:
Notify your author-
ised electrician.
E
FS
93,
94
Self test error
Buff er 1, Buff er 2
The control board is defective.
Notify authorised
electrician / KACO
Service
E/K
FS
95,
96
Self test error
Relay 1, Relay 2
The power section is defective.
Notify KACO Service
K
FS
97
Protection shut-
down overcur-
rent HW
Too much power has been fed into the
grid. Complete disconnection of the
device.
Notify authorised
electrician / KACO
Service
E/K
FS
98,
99
Protection shut-
down HW gate
driver/
HW buff er-free.
An internal protective mechanism has
disconnected the device to protect it
against damage.
Complete disconnection of the device.
Notify authorised
electrician / KACO
Service
E/K
Table 6:
Operating status and fault messages on the display