6mounting the inverter, Installation space, Floor and wall – KACO Powador 30.0 - 60.0 TL3 User Manual
Page 15
Mounting the inverter
Operating Instructions for Powador 30.0-72.0 TL3_EN
Page 15
EN
Authorised electrician
6
Mounting the inverter
DANGER
Risk of fatal injury from fi re or explosions
Fire caused by fl ammable or explosive materials in the vicinity of the inverter can lead to serious
injuries.
›
Do not mount the inverter in an area at risk of explosion or in the vicinity of highly fl ammable mate-
rials.
Installation space
•
As dry as possible, climate-controlled, with the waste heat dissipated away from the inverter
•
Air circulation should not be blocked
•
When installing the unit in a control cabinet, provide forced ventilation so that the heat is suffi
ciently dissipated
•
Close to the ground, accessible from the front and sides without requiring additional resources
•
Protected on all sides against heavy rain and direct sunlight (thermal heating) in outdoor areas.
Implementation where necessary via constructional measures, e.g. wind breaks.
•
For easy operation, ensure during installation that the display is slightly below eye level.
Floor and wall
•
With suffi
cient load-bearing capacity
•
Accessible for installation and maintenance
•
Made from heat-resistant material (up to 90 °C),
•
Flame resistant
•
minimum clearances for installation: see on page 15 and on page 15.
NOTE
Access by maintenance personnel for service
Any additional costs arising from unfavourable structural or mounting conditions shall be billed to
the customer.
CAUTION
Property damage due to gases that have an abrasive eff ect on surfaces when they come into
contact with ambient humidity caused by weather conditions.
The inverter housing can be severely damaged by gases (ammonia, sulphur, etc.) if it comes
into contact with ambient humidity caused by weather conditions.
If the inverter is exposed to gases, it must be mounted so that it can be seen at all times.
›
Perform regular visual inspections.
›
Immediately remove any moisture from the housing.
›
Take care to ensure suffi
cient ventilation of the inverter.
›
Immediately remove dirt, especially on vents.
›
Failure to observe these warnings may lead to inverter damage which is not covered by the KACO
new energy GmbH manufacturer warranty.