Configuration and operation – KACO Powador 30.0 - 60.0 TL3 User Manual
Page 39
Configuration and Operation
Operating Instructions for Powador 30.0-72.0 TL3_EN
Page 39
EN
Coun-
try-spec.
setting
menu
level
Display/
setting
Action in this menu/meaning
BG, FR, CZ,
UD
4
1
2
3
1
Voltage drop
The voltage drop between the inverter and the feed-in
meter is added to the limit value that was set for grid
shutdown according to EN 50160. The limit value can be
set from 0 to 11 V in 1 V increments.
Specify the switch-off value for the voltage drop (0
to 11 V).
DE-MSp, FR,
GB, HU, IL, IN,
IT, AT, PL, RU,
ES, TH, ZA,
UD
4
1
2
3
1
Undervoltage
shutd.
Specify the shutdown threshold
for fast and slow undervoltage shutdown.
Set period from occurrence of the fault to shutdown
of the inverter.
DE-MSP, FR,
GB, IN, IT, AT,
PL, RU, ES,
TH, ZA, UD
4
1
2
3
1
Overfreq. shutd.
Set limit value for overfrequency shutdown.
4
1
2
3
1
Underfreq. shutd.
Set limit value for the underfrequency shutdown.
FR, IL, IN, IT,
AT, PL, RU,
TH, ZA, UD
4
1
2
3
1
Activation
condition
The inverter checks mains voltage and frequency. The
grid feed operation begins if the measured values are
within the set ranges.
Set minimum and maximum values for the switch-
ing on.
DE, BE, FR,
GB, IL, IN, IT,
AT, PL, RU, ES,
TH, ZA, UD
4
1
2
3
1
Connect time
Set period for grid observation (in seconds) when
switching on and reconnection after a fault.
ZA, UD
4
1
2
3
1
Power reduction
P(f)
Activates the power reduction with selection of an
operating mode P(f )
For selected mode OFF, 1 or 2
enter P(f ) thresholds and gradient.
IL, IT, ZA, UD
4
1
2
3
1
P(f) Gradient
Set gradient of power limit function with increasing
frequency in % / Hz. This percentage relates to the
nominal frequency of 50 Hz
IL, IT, ZA, UD
4
1
2
3
1
P(f) thresholds
Set the frequency thresholds for activating and
deactivating the power limitation in Hz.
4
1
2
3
1
DC starting volt.
The inverter begins feed-in as soon as this DC voltage is
present.
Set the starting voltage.
4
1
2
3
1
DC-OVP-Monitor.
Allows the monitoring of the integrated overvoltage
protection.
Activate overvoltage protection.
NOTE: By activating, an overvoltage protection test is
carried out with an appropriate status message.
4
1
2
3
1
Const. volt. ctrl.
Lets you deactivate the MPP seek mode in order to oper-
ate the inverter with a constant DC voltage.
Activate or deactivate the constant voltage
controller.
Set value for constant voltage control (200 - 800 V).
NOTE: For voltages below the minimal MPP voltage the
possible input power is reduced. The input current is
limited to 34 A per input.