Configuration and Operation

Operating Instructions for Powador 30.0-72.0 TL3_EN

Page 39

EN

Coun-

try-spec.

setting

menu

level

Display/

setting

Action in this menu/meaning

BG, FR, CZ,

UD

4

1

2

3

1

Voltage drop

The voltage drop between the inverter and the feed-in
meter is added to the limit value that was set for grid
shutdown according to EN 50160. The limit value can be
set from 0 to 11 V in 1 V increments.

 Specify the switch-off value for the voltage drop (0

to 11 V).

DE-MSp, FR,

GB, HU, IL, IN,

IT, AT, PL, RU,

ES, TH, ZA,

UD

4

1

2

3

1

Undervoltage

shutd.

 Specify the shutdown threshold

for fast and slow undervoltage shutdown.

 Set period from occurrence of the fault to shutdown

of the inverter.

DE-MSP, FR,

GB, IN, IT, AT,

PL, RU, ES,

TH, ZA, UD

4

1

2

3

1

Overfreq. shutd.

 Set limit value for overfrequency shutdown.

4

1

2

3

1

Underfreq. shutd.

 Set limit value for the underfrequency shutdown.

FR, IL, IN, IT,

AT, PL, RU,

TH, ZA, UD

4

1

2

3

1

Activation

condition

The inverter checks mains voltage and frequency. The
grid feed operation begins if the measured values are
within the set ranges.

 Set minimum and maximum values for the switch-

ing on.

DE, BE, FR,

GB, IL, IN, IT,

AT, PL, RU, ES,

TH, ZA, UD

4

1

2

3

1

Connect time

 Set period for grid observation (in seconds) when

switching on and reconnection after a fault.

ZA, UD

4

1

2

3

1

Power reduction

P(f)

 Activates the power reduction with selection of an

operating mode P(f )

 For selected mode OFF, 1 or 2

enter P(f ) thresholds and gradient.

IL, IT, ZA, UD

4

1

2

3

1

P(f) Gradient

 Set gradient of power limit function with increasing

frequency in % / Hz. This percentage relates to the
nominal frequency of 50 Hz

IL, IT, ZA, UD

4

1

2

3

1

P(f) thresholds

 Set the frequency thresholds for activating and

deactivating the power limitation in Hz.

4

1

2

3

1

DC starting volt.

The inverter begins feed-in as soon as this DC voltage is
present.

 Set the starting voltage.

4

1

2

3

1

DC-OVP-Monitor.

Allows the monitoring of the integrated overvoltage
protection.

 Activate overvoltage protection.

NOTE: By activating, an overvoltage protection test is
carried out with an appropriate status message.

4

1

2

3

1

Const. volt. ctrl.

Lets you deactivate the MPP seek mode in order to oper-
ate the inverter with a constant DC voltage.

 Activate or deactivate the constant voltage

controller.

 Set value for constant voltage control (200 - 800 V).

NOTE: For voltages below the minimal MPP voltage the
possible input power is reduced. The input current is
limited to 34  A per input.