Installing the inverter

Operating Instructions for Powador 30.0-72.0 TL3_EN

Page 23

EN

Authorised electrician

Delivery state as well as the type and number of the string fuses supplied:

Equipment types

Delivery state

Fuses supplied

Powador 30.0 - 48.0 TL3 XL

Short circuit bridge in string fuse 1 of
MPP trackers 1, 2 and 3

12x PV fuse 10 x 38mm, 15 A, 1000V/DC

Powador 60.0 - 72.0 TL3 XL

15x PV fuse 10 x 38mm, 15 A, 1000V/DC

Insert string fuses

↻ Device switched OFF from DC isolator switch
1.

Open fuse holder.

2. Remove and store short-circuit bridges.

3. Insert suitable string fuses into the DC positive fuse holders.

4. Close the fuse holders.

»

Continue connecting the PV generator.

7.3.2.3

Recommended standard connection for Powador 39.0 TL3 XL/60.0 TL3 XL

DANGER

Risk of fatal injury due to electric shock (electric arc)!

Wrong assignment of MPP trackers will seriously damage the inverter.

Severe injury or death will result if the live connections are touched.

Make sure that each MPP tracker can be disconnected from all poles.

Observe recommended standard connection.

NOTE

The recommended standard connection is only applicable for version XL devices. This is the only
device version with an integrated combiner box.

The strings connected to a MPP tracker must all have the same MPP voltage.

The MPP voltages of the three independently functioning MPP trackers 1, 2 and 3 may diff er within the working area,
however.

Electrical data for standard connection

Number of modules per
string

P

max

I

max

per MPP tracker

39.0 TL3 XL

On each MPP tracker:
n

1

=n

2

=n

3

=n

4

per MPP tracker < 13 kW

MPP trackers 1+2+3 together < 39 kW

<34.0 A

60.0 TL3 XL

On each MPP tracker
n

1

=n

2

=n

3

=n

4

=n

5

per MPP tracker < 20 kW

MPP trackers 1+2+3 together < 60 kW

<36,0 A