KACO Powador 30.0 - 60.0 TL3 User Manual
Page 11
Technical Data
Operating Instructions for Powador 30.0-72.0 TL3_EN
Page 11
EN
Input levels
40.0 TL3
48.0 TL3
Park
60.0 TL3
72.0 TL3
Park
DC MPP range from [V] to [V]*
350 ... 800
410 ... 800
480 ... 850
580 ... 850
Operating range from [V] to [V]
200 ... 800
200 ... 800
200 ... 850
200 ... 850
Starting voltage [V]**
250
Open circuit voltage [V]
1 000 (start to 950)
Rated current max. [A]
3 x 34.0
3 x 34.0
3 x 36.0
3 x 36.0
Max. power per tracker [W]
20,000
20,000
20,000
24,000
Number of strings
3 x 1 (M)
3 x 4 (XL)
3 x 1 (M)
3 x 4 (XL)
3 x 1 (M)
3 x 4 (XL)
3 x 1 (M)
3 x 5 (XL)
3 x 4 (F)
Number of MPP trackers
3
Polarity safeguard
Short-circuit diode
*At DC voltages below the MPP range the maximum rated current reduces the maximum input power.
**For PV generators with MPP voltages below the MPP range of the inverter: set the start voltage in the menu.
Output levels
Rated power [VA]
36,000
40,000
49,900
60,000
Grid voltage [V]
230 / 400
277 / 480***
230 / 400
277 / 480***
Rated current [A]
3 x 52.2
3 x 48.1
3 x 72.2
3 x 72.2
Rated frequency [Hz]
50/60
cos phi
0.80 inductive to 0.80 capacitive
Number of feed-in phases
3
Distortion factor [%]
< 3
***Device is designed for use exclusively on the medium-voltage grid.
General electrical data
Max. effi
ciency [%]
98.0
98.0
97.9
98.3
European effi
ciency [%]
97.8
97.9
97.7
98.0
Make current [A] / ON duration [ms]
98 / 4.4
Internal consumption: standby [W]
< 30
Internal consumption: night [W]
~1.5
Feed-in starts at [W]
120
Circuit design
IGBT, self-commutated, transformerless
Grid monitoring
Country-specifi c
CE conformity
Yes
Table 2:
Electrical data