4) lt_sgnl specifications, 5) related parameters – Yaskawa Sigma-5 User Manual: MECHATROLINK-II Commands User Manual
Page 72

4.2 Motion Commands Details
4-7
4
Motion Commands for Operation
Latched Position Data
The latest latched position data at completion of latching can be obtained by using the following monitor.
The previously latched position data can be obtained by using the following option monitor.
(4) LT_SGNL Specifications
• Applicable Commands:
LATCH, EX_POSING, ZRET, LTMOD_ON (when Pn850=0), SVCTRL
The latch signals can be specified in the following latch signal (LT_SGNL) field.
Note: The EXT2 and EXT3 cannot be used with DC power input
Σ-V series SERVOPACKs (SGDV-E11).
(5) Related Parameters
The parameters related to latch operation are listed below.
Note 1. EXT1, EXT2, and EXT3 signals must be assigned as the input signals of CN1 by using the parameter Pn511. If
they are not assigned, the latch operation will be undefined.
2. If encoders without phase C (origin signal) and linear scales are used and the phase C is selected, the latch opera-
tion will be undefined.
Name
Code
Remarks
Feedback Latch Position
LPOS
The latest latch signal input position
Name
Code
Option Monitor Selection
(Pn824 and Pn825)
Option Monitor 1 and 2
OMN1, 2
80H: Previous latch signal input position
D7
D6
D5
D4
D3
D2
D1
D0
0
0
0
0
0
0
LT_SGNL
D1
D0
Latch Signal
Signal Details
0
0
Phase C
Encoder origin signal
0
1
EXT1
External input signal 1
1
0
EXT2
External input signal 2
1
1
EXT3
External input signal 3
Parameter No.
Name
Pn820
Forward Latching Allowable Area
Pn822
Reverse Latching Allowable Area
Pn850
Latch Sequence Number
Pn851
Continuous Latch Count
Pn852 and Pn853
Latch Sequence Signal Setting