8 Detecting Alarms/Warnings Related to Communications or Commands
8-2
8.1 List of Alarms
The following table shows alarms that are related to communications or commands and that may occur in
MECHATROLINK-II communications.
If an error is found in the command or data that a SERVOPACK has received, the SERVOPACK returns the
corresponding alarm number.
At the same time, the alarm number is displayed on the SERVOPACK.
Servomotor Stopping Method
If an alarm occurs, the servomotor can be stopped by doing either of the following operations.
Gr.1: The servomotor is stopped according to the setting in Pn001.0 if an alarm occurs. Pn001.0 is factory-set
to stop the servomotor by applying the DB.
Gr.2: The servomotor is stopped according to the setting in Pn00B.1 if an alarm occurs. Pn00B.1 is factory-set
to stop the servomotor by setting the speed reference to
"
0.
"
The servomotor under torque (force) con-
trol will always use the Gr.1 method to stop. By setting Pn00B.1 to 1, the servomotor stops using the
same method as Gr.1. When coordinating a number of servomotors, use this stopping method to prevent
machine damage that may result due to differences in the stop method.
Alarm Reset
Available: Removing the cause of alarm and then executing the alarm reset can clear the alarm.
N/A:
Executing the alarm reset cannot clear the alarm.
Alarm Number:
Alarm Name
(Alarm Description)
Cause
Investigative Actions
Corrective Actions
SERVOPACK Side
Servomotor
Stopping
Method
Alarm
Reset
A.b6A:
MECHATROLINK
Communications ASIC
Error 1
SERVOPACK MECHA-
TROLINK communica-
tion section fault.
−
Replace the SERVOPACK.
Gr.1
N/A
A.E02:
MECHATROLINK-II
Internal
Synchronization
Error 1
MECHATROLINK-II
transmission cycle fluc-
tuated.
−
Remove the cause of trans-
mission cycle fluctuation at
host controller.
Gr.1
Available
A SERVOPACK fault
occurred.
−
Turn the power supply OFF
and then ON again. If the
alarm still occurs, the SER-
VOPACK may be faulty.
Replace the SERVOPACK.
A.E40:
MECHATROLINK-II
Transmission Cycle
Setting Error
Setting of MECHA-
TROLINK-II transmis-
sion cycle is out of
specifications range.
Check the MECHA-
TROLINK-II transmis-
sion cycle setting.
Set the transmission cycle to
the proper value.
Gr.2
Available
A.E50:
MECHATROLINK-II
Synchronization Error
WDT data of host con-
troller was not updated
correctly.
Check the WDT data
updating for the host
controller.
Update the WDT data at the
host controller correctly.
Gr.2
Available
A SERVOPACK fault
occurred.
−
Turn the power supply OFF
and then ON again. If the
alarm still occurs, the SER-
VOPACK may be faulty.
Replace the SERVOPACK.