3.2 Digital Output Module Specifications

3-37

3

2) The following diagram shows the circuit configuration.

If using a 12/24-VDC 16-point Output Module (sinking), connect a fuse, which
complies with the load specifications, in series with the load.

A protective fuse built into the following 12/24-VDC 16-point Output Modules
does not protect the output element. If a fuse is not connected, a fire or dam-
age to the devices or output circuits may occur if the load is short-circuited or
the circuit overloaded.

Output 1

Output 8

-Common 1

Output 9

Output 16

- Common 2

12/24 VDC

12/24 VDC

Output signal
indicator

From CPU

Photocoupler

+ Common 1

+ Common

Loads

Loads

Fuse

Blown fuse
Power not
connected
indicator

Blown fuse
detection circuit

Internal circuits

CAUTION