3 12/24-vdc 8-point output module – Yaskawa 120 Series I/O Modules User Manual
Page 62

3 Digital I/O Specifications
3.2.3 12/24-VDC 8-point Output Module
3-32
3.2.3
12/24-VDC 8-point Output Module
1) Performance Specifications
Item
Specifications
Name
12/24-VDC 8-point Output Module
Model Name
DC24OUT-8P
Model No.
JAMSC-120DDO33000
Rated Voltage
12/24 VDC
Allowable Voltage Range
10.2 to 30.0 VDC
Output Form
Sourcing or sinking
Maximum Load Current
2.0 A/point
Output Voltage Drop
0.1 V max (2.0 A)
Output Delay Times
OFF to ON: 3 ms max.
ON to OFF: 5 ms max.
OFF Leakage Current
1 mA max. at 24 VDC
Output Type
Transistor (FET) outputs
Number of Commons
8 (Each output circuit is independent.)
External Connections
Removable terminal block with M3 screw terminals
Output Protection Type
Protected outputs (according to JIS B3502)
Built-in Fuse
Eight, 3.5-A fuses (one per circuit)
(Burnout time: 1 s max. at 200% of rated current)
Surge Suppressor
Zener diode
Other Output Protection
None
Number of Outputs
8
Output Signal Indication
Indicator for each point; lit when the output is ON.
Status saved in internal logic.
Status Indication
ACTIVE: Lights during output processing.
Insulation Method
Photocoupler
Dielectric Strength
1,500 VAC for 1 min or 1,800 VAC for 1 s between output
terminals and internal circuits
Insulation Resistance
100 M
Ω min. at room temperature and humidity between
output terminals (connected together)
and ground
(measured with a 500-VDC test voltage megohmmeter).
External Power Supply
12/24 VDC supplied to drive loads
Derating Conditions
None
Internal Current Consumption
220 mA max. at 5 VDC (with all points ON)
Maximum Heating Value
1.6 W
Hot Swapping
(Removal/insertion under power)
Permitted
Approximate Mass
250 g
External Dimensions
40.3
×130×103.9 mm (W×H×D)