beautypg.com

Example – Yaskawa 120 Series I/O Modules User Manual

Page 46

background image

3 Digital I/O Specifications

3.1.4 12/24-VDC 32-point Input Module

3-16

3) The following diagram shows an example or terminal connections.

Note: (1) Pins 9 and 29, pins 19 and 39 are internally connected.

Connect these pins externally as well. Not connecting
them can cause malfunction.

(2) Connectors for External Connections

On the Module: 10240-52A2JL (manufactured by 3M)

(3) Recommended wires

Use wires of 0.08mm

2

(AWG28) to connect to each pin of

the connector.

(4) The polarity of the external power supply for signals can be

connected with either plus or minus.

(5) Pins 10, 20, 30, and 40 are not connected.
(6) External Connection Cable

Use a 32-point I/O Module Cable to connect to field
devices. Refer to 3.3 I/O Module Cables for details.

Input 32

Common 2

Not

connected

Not

connected

Input 30

Input 28

Input 26

Input 24

Input 22

Input 20

Input 18

Not

connected

Not

connected

Common 1

Input 31

Input 29

Input 27

Input 25

Input 23

Input 21

Input 19

Input 17

Input 16

Input 14

Input 12

Input 10

Input 8

Input 6

Input 4

Input 2

Input 15

Input 13

Input 11

Input 9

Input 7

Input 5

Input 3

Input 1

12/24 VDC

12/24 VDC

Pin No.

Pin No.

EXAMPLE