5 12/24-vdc 64-point input module – Yaskawa 120 Series I/O Modules User Manual
Page 48

3 Digital I/O Specifications
3.1.5 12/24-VDC 64-point Input Module
3-18
Note: (1) The symbol “ -” in the type stands for length for the cable. See 3.3 I/O Mod-
ule Cables for details.
(2) The terminal block number for the 32-point I/O connector type (manufactured
by OMRON) is not that same as that for the 12/24-VDC 32-point Output Mod-
ule. Refer to 3.3 I/O Module Cables for details.
3.1.5
12/24-VDC 64-point Input Module
1) Performance Specifications
The Module does not conform to JIS B3502 when used as a 12-VDC Module.
Item
Specification
At 12 VDC
At 24 VDC
Name
12/24-VDC 64-point Input Module
Model Name
DC24IN-64P
Model No.
JAMSC-120DDI36400
Rated Voltage
12/24 VDC
Maximum Allowable
Voltage
30 VDC
Input Form
Sourcing or sinking
Rated Current
2 mA
4 mA
Input Impedance
5.6 k
Ω
Standard Operating
Ranges
Minimum ON voltage: 9 VDC
Maximum OFF voltage: 5 VDC
Input Type
Does not conform to JIS B3502.
DC type 2 (according to JIS B3502)
Input Delay Times
OFF to ON: 5 ms max.
ON to OFF: 5 ms max.
Number of Commons
4
Number of Inputs per
Common
16 points/common
External Connections
40-pin connector: 2 pieces
Connector type: FCN-365P040 (made by Fujitsu)
Number of Inputs
64
Input Signal Indica-
tion
Indicator for each point; lit when the input is ON.
Status saved in internal logic.
32 indicators controlled by toggle switches
Status Indication
ACTIVE: Lights during input processing
Insulation Method
Photocoupler
Dielectric Strength
1,500 VAC for 1 min or 1,800 VAC for 1 s between input terminals and
internal circuits and between all input commons
Insulation Resistance
100 M
Ω min. at room temperature and humidity between input terminals
and ground (measured with a 500-VDC test voltage megohmmeter).
External Power Sup-
ply
12 VDC supplied to signals
24 VDC supplied to signals
Derating Conditions
None
Internal Current Con-
sumption
100 mA max. at 5 VDC (with all points ON)
Maximum Heating
Value
7.0 W